1-805-484-2992

Quotes - Sizing - Sales

POC-500G-60

Filtrine
Product Type Capacity Refrigerant
Recirculating Chiller Air-Cooled 2.92 Tons @ 50°F HFC

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n POC-500G-60 as shown on this page.

Replacement chiller for the Filtrine POC-500G-60

Description

The Filtrine POC-500G-60 is a 2.92-ton open-loop recirculating air-cooled chiller from the POC line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 35,000 Btu/h, 2.92 tons, at 50°F outlet and 90°F ambient, 25,000 Btu/h at 30°F and 60,000 Btu/h at 68°F, the point its model number is named for. As an open-loop chiller its pump draws from an open tank or sump and returns to it, with the thermostat sensing the make-up liquid. Replacement: we supply the Temptek CG-4A, an air-cooled portable chiller rated 4 tons at 50°F, against the 2.92 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin. The Temptek unit runs a closed loop from its own tank, so an open sump on the old system is piped as the return or replaced.

Product Overview

Part Number:
POC-500G-60
Manufacturer:
Filtrine
Replacement Unit:
Temptek CG-4A

Published Capacity

Cooling Capacity at 50°F:
35,000 Btu/h (2.92 tons)
Cooling Capacity at 30°F:
25,000 Btu/h
Cooling Capacity at 68°F:
60,000 Btu/h
Rating Point:
90°F ambient, air-cooled (-A) model
Thermostat Range:
40 to 90°F standard

Configuration & Specifications

Style:
Open-loop recirculating
Compressor:
Scroll, 5 hp
Condenser:
Fan-cooled (-A); water-cooled (-W) offered
Evaporator:
Immersion coil in a welded stainless tank
Refrigerant:
HFC (per the spec sheet)

Pump & Reservoir

  • Pump: 3/4 hp
  • Cooling Tank: 50 gallons

Electrical

  • Supply Power: 208-230 V, 3 ph, 60 Hz or 460 V, 3 ph, 60 Hz

Connections

Plumbing Connections In & Out:
1 in MPT

Dimensions & Weight

Cabinet (W x D x H):
72 x 35 x 60 in
Shipping Weight:
1,800 lbs

Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales