| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chiller Module | Add-On Module | 9.5 Tons @ 40°F | R-404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n GD-13.5H-EM as shown on this page.
The G&D Chillers GD-13.5H-EM is an expansion chiller module (refrigeration only, no reservoir or process pump) from G&D's Expansion Module Series. G&D publishes it at 114,193 Btu/h at 40°F leaving glycol (about 9.5 tons), 95,082 at 30°F, 77,911 at 20°F, in a 90°F ambient, on R-404A. It carries a 13.5 HP compressor and a 1 HP circulation pump. Replacement: we supply the Temptek MA-20-RC-C, an air-cooled chilling module rated 19 tons at 50°F, about 7.6 tons at 20°F on Temptek's published 0.40 multiplier, against the 6.5 tons G&D publishes for this unit at 20°F (its coldest published rating), so it covers every published setpoint. It carries its refrigeration on one frame with a remote air-cooled condenser.
Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.