1-805-484-2992

Quotes - Sizing - Sales

GD-20H-2LC

G&D Chillers
Product Type Capacity Refrigerant
Low-Temp Chiller Ultra-Low Temp 6.6 Tons @ -30°F R-404A

Note: Unit pictured is representative of the form factor only and does not depict p/n GD-20H-2LC as shown on this page.

Representative outdoor chiller, not the G&D GD-20H-2LC

Description

The G&D Chillers GD-20H-2LC is an ultra-low temperature chiller on two-stage compressors from G&D's LSX Ultra-Low Temp Series. G&D publishes it at 79,600 Btu/h at -30°F coolant (about 6.6 tons), 60,500 at -40°F, 45,800 at -50°F, in a 90°F ambient, on R-404A. It carries two 10 HP two-stage reciprocating compressors, a 50-gallon reservoir and a 3 HP process pump delivering 20 GPM at 25 PSI. Replacement: nothing we supply is rated at these coolant temperatures, so there is no like-for-like unit. Talk to an application specialist with the process temperature and load.

Product Overview

Part Number:
GD-20H-2LC
Spec Sheet Model:
GD-20H-2LC-VA2
Manufacturer:
G&D Chillers
Replacement Unit:
Application specialist

Published Capacity

Capacity at -30°F Coolant:
79,600 Btu/h (23.3 kW)
Capacity at -40°F Coolant:
60,500 Btu/h (17.7 kW)
Capacity at -50°F Coolant:
45,800 Btu/h (13.4 kW)
Rating Basis:
90°F ambient

Configuration & Specifications

Compressor:
10 HP Two-Stage Recip (x2)
Refrigerant:
R-404A
Condenser:
Air-Cooled Vertical Discharge
Evaporator:
Stainless Steel Brazed Plate
Controls:
Microprocessor w/ Comm.
Housing:
Powder Coated Aluminum
Electrical Enclosure:
NEMA 3R
Sound Level:
75 dBA at 10 ft

Pump & Reservoir

  • Reservoir: 50 Gallon
  • Process Pump: 3 HP
  • Process Flow: 20 GPM at 25 PSI
  • Connection Size: 1"

Electrical

  • Voltage: 230V / 460V
  • Phase: Three Phase
  • Full Load Amps: 106 (230V) / 55 (460V)
  • Minimum Circuit Ampacity: 117 (230V) / 60 (460V)
  • Maximum Overcurrent Protection: 161 (230V) / 83 (460V)

Dimensions & Weight

Dimensions (W x L x H):
45" x 140" x 102"
Operating Weight:
3,600 lbs
Shipping Weight:
3,000 lbs

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992