| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Low-Temp Chiller | Ultra-Low Temp | 11.2 Tons @ -30°F | R-404A |
Note: Unit pictured is representative of the form factor only and does not depict p/n GD-40H-2LC as shown on this page.
The G&D Chillers GD-40H-2LC is an ultra-low temperature chiller on two-stage compressors from G&D's LSX Ultra-Low Temp Series. G&D publishes it at 135,000 Btu/h at -30°F coolant (about 11.2 tons), 102,600 at -40°F, 76,900 at -50°F, in a 90°F ambient, on R-404A. It carries two 20 HP two-stage reciprocating compressors, a 90-gallon reservoir and a 5 HP process pump delivering 42.5 GPM at 25 PSI. Replacement: nothing we supply is rated at these coolant temperatures, so there is no like-for-like unit. Talk to an application specialist with the process temperature and load.
Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.