| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Outdoor Packaged | 8.2 Tons @ 40°F | R-448A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n GD-10H as shown on this page.
The G&D Chillers GD-10H is a single-compressor packaged glycol chiller from G&D's Single Stage Series, sold as the Micro Chill. G&D publishes it at 98,000 Btu/h at 40°F leaving glycol (about 8.2 tons), 80,000 at 30°F, 64,000 at 20°F, in a 90°F ambient, on R-448A. It carries a 10 HP compressor, a 110-gallon reservoir and a 2 HP process pump delivering 65 GPM at 25 PSI. Replacement: we supply the Temptek TTOACS-15S-CG-1P, an outdoor air-cooled packaged chiller rated 14.4 tons at 50°F, about 5.8 tons at 20°F on Temptek's published 0.40 multiplier, against the 5.3 tons G&D publishes for this unit at 20°F (its coldest published rating), so it covers every published setpoint.
Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.