| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Outdoor Packaged | 140 Tons @ 40°F | R-454C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n GD-240H-6C as shown on this page.
The G&D Chillers GD-240H-6C is a packaged glycol chiller on semi-hermetic compressors from G&D's Vertical Air Series. G&D publishes it at 1,676,000 Btu/h at 40°F leaving glycol (about 140 tons), 1,402,000 at 30°F, 1,136,000 at 20°F, in a 90°F ambient, on R-454C. It carries six 40 HP compressors, a 1,400-gallon reservoir and a 15 HP process pump delivering 470 GPM at 25 PSI. Replacement: no Temptek unit reaches this size, so we supply it from our sister line: outdoor air-cooled central chillers to 210 tons, paired where the load is larger than one unit.
Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.