Vertical Air Series

G&D's large packaged glycol plants: 30 to 300 HP on semi-hermetic compressors, with vertical-discharge condensers and tanks up to 1,400 gallons.

PRODUCT TYPE CAPACITY MODELS
Glycol Chiller Outdoor Packaged 23 to 181 Tons 12

Specifications


Configuration & Size

Capacity:
23 to 181 Tons at 40°F
Models:
12 part numbers
Compressor:
Semi-hermetic, 1 to 6
Process Flow:
150 to 550 GPM
Refrigerant:
R-454C

Construction

  • Semi-hermetic compressors with unloaders
  • Vertical-discharge air-cooled condenser
  • Stainless glycol reservoir
  • Separate process and chiller pumps
  • Liquid receivers and filter dryers

Ratings

  • Rated at 20, 30 and 40°F glycol
  • 10°F difference, 90°F ambient
  • Refrigerant R-454C
  • Power: 208-240/3 to 100 HP, 460-480/3

Specifications sourced from G&D Chillers' published product pages, spec sheets and brochures (gdchillers.com), September 2026. G&D Chillers, Nano Chill, Micro Chill and Fire & Ice are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Vertical Air Glycol Chillers, 30 to 300 HP

The Production Brewery Plant

Twelve models, one to six semi-hermetic compressors each. The Vertical Air line uses reciprocating compressors with capacity unloading, from a single 35 HP machine on the GD-35H-1C to six 50 HP machines on the GD-300H-6C, all on R-454C.

Capacity at 40°F runs from 272,300 to 2,175,000 Btu/h, about 23 to 181 tons, with a 10°F temperature difference in a 90°F ambient at sea level. At 20°F the range is 176,000 to 1,495,400 Btu/h.

The package includes the plant. A stainless reservoir of 235 to 1,400 gallons, a process pump of 5 to 20 HP delivering 150 to 550 GPM, and a separate chiller pump, all on one frame with a vertical-discharge air-cooled condenser.

Voltage narrows as the units grow. Up to the GD-100H-2C the line is listed on 208-240 V and 460-480 V three-phase; from the GD-140H-4C up, 460-480 V only.



stainless columns, tanks and blue pumps in a solvent recovery plant

Semi-hermetic compressors, a stainless tank the size of a small room, and a pump sized for the whole cellar.

Request a Quote

Vertical Air Series Applications

Production breweries
Production breweries
Large wineries
Large wineries
Dairy and food plants
Dairy and food plants
Cold rooms and storage
Cold rooms and storage

schematic of the Vertical Air series circuit, showing where the process fluid and the condenser heat go

Vertical Discharge on a Crowded Site

The condenser fans blow straight up, which is why G&D calls this the Vertical Air line. Hot air goes above the unit instead of across the site, so two units can sit closer together and closer to a wall without breathing each other's exhaust. Clearance still matters on the coil side, and a unit boxed in by walls on three sides will run above its 90°F rating ambient on a hot afternoon.

At this size the pumps are a real part of the selection. The process pump is sized for the plant loop, the chiller pump for the evaporator, and the reservoir decouples them. When replacing one, check that the new unit's process pump matches the head of the existing header, not just its flow.

Each part-number page below names the Temptek outdoor unit we supply in its place, sized to cover the published capacity at 20°F, the coldest point G&D rates. At that point the GD-200H-4C, GD-240H-6C and GD-300H-6C are beyond the largest Temptek unit, and their pages point to the largest outdoor units on our sister site.
Call and talk it through with an engineer: 1-805-484-2992

Vertical Air Plants in Practice

The suffix counts compressors, so the GD-150H-3C runs three 50 HP machines and the GD-160H-4C four 40 HP machines. Leaving the unloaders aside, the first steps in thirds and the second in quarters, so the four-compressor unit follows a light winter load with smaller swings in tank temperature. With one compressor down, the 3C keeps about two-thirds of its capacity and the 4C about three-quarters. The number ahead of the H is total horsepower, which is why the GD-240H-6C, six 40 HP machines, and the GD-300H-6C, six 50s, share a suffix and differ by 60 HP.

The current explains it: the GD-100H-2C already draws 443 full load amps on 208-240 V, against 231 on 460-480 V. Larger units would roughly double their 460-480 V figures on the lower voltage, and the GD-300H-6C draws 657 amps even at 460-480 V. A plant with only 208 V service that is growing past 100 HP faces a transformer or a utility upgrade as part of the project, so raise it at the start. Every model from the GD-140H-4C up is listed on 460-480 V only.

The published capacity assumes return glycol 10°F warmer than supply, which on the water formula is about 1 GPM for every 5,000 Btu/h. The smallest unit's 272,300 Btu/h at 40°F implies roughly 54 GPM, and the largest unit's 2,175,000 Btu/h roughly 435 GPM, both below what the 150 to 550 GPM process pumps deliver. A loop that returns only 5°F warmer carries half the heat per gallon, so either the flow doubles or the unit never reaches its published capacity, and glycol needs a little more flow than water either way. Measure supply and return temperatures at full load before comparing. The same arithmetic shows why the 20°F figures matter for the pump: the smallest unit's 176,000 Btu/h at 20°F needs only about 35 GPM at a 10°F rise, so a small unit on a large process pump runs a narrow rise across the plant, which is normal for this line and not a fault.

Not exactly, because the line is rated at sea level as well as in a 90°F ambient. Thinner air carries less heat across the condenser coil for the same fan speed, so the condensing temperature runs higher and capacity falls as elevation rises. The ratings quoted here carry no altitude correction, so give us the site elevation with the setpoint and the selection carries it.

Tight, about 3 percent. The GD-160H-4C is published at 66 tons at 20°F, and the Temptek TTOACS-190D-MZC-2P we supply in it's place makes about 68 tons there on the 0.40 multiplier. That is the largest Vertical Air size the Temptek outdoor range covers; the GD-200H-4C, GD-240H-6C and GD-300H-6C exceed it at 20°F and go to our sister line's outdoor central chillers, up to 210 tons a unit, in pairs where needed. With so little margin, a unit hemmed in by walls, or a site that sees summers past the 90°F rating ambient, should be reviewed with us before ordering.

Quote Request Form: