| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Process Chiller | Air-Cooled | 46.89 Tons nominal | R290 (propane) (series datasheet) |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n IC050n as shown on this page.
The ICS IC050n is an i-Chiller from the i-Chiller Process Max n line, a large propane (R290) air-cooled chiller built for 400 V / 50 Hz supply. ICS lists a nominal cooling capacity of 164.9 kW, about 46.89 tons. It runs on R290 (propane). Replacement: we supply the Temptek TTOACS-80D-MZC-2P, a dual-zone outdoor air-cooled packaged chiller rated 75.8 tons at 50°F, against the 46.89 tons ICS Cool Energy publishes for this unit at its nominal rating. ICS publishes a nominal kW figure; its Compact-n datasheet gives the EN 14511 rating point of 12/7°C water and 35°C ambient, colder than Temptek's 50°F. The pick is sized on Temptek's published 40°F multiplier of 0.80, which covers a 7°C (44.6°F) rating or any warmer one, and is confirmed against your set point before quoting. Divided by 0.80, the 46.89 tons call for at least 58.61 tons of Temptek 50°F rating. The Temptek unit is built for North American 460 V / 60 Hz or 230 V supply, not 400 V / 50 Hz.
Specifications sourced from ICS Cool Energy's published i-Chiller product pages and datasheets (icscoolenergy.com), October 2026. ICS Cool Energy and i-Chiller are trademarks of their owner; referenced here for cross-reference only. Capacities are ICS's nominal figures in kW, converted at 3.517 kW per ton. Confirm against the unit nameplate before ordering.