i-Chiller Process Max n Series

ICS's large natural-refrigerant chiller: the Process Max n on R290 propane, 164.9 to 241.5 kW nominal.

PRODUCT TYPE CAPACITY MODELS
Process Chiller Large, R290 165 to 242 kW 3

Specifications


Configuration & Size

Capacity:
164.9 to 241.5 kW nominal
Models:
3 part numbers
Refrigerant:
R290 propane
Circuits:
2 / 4 or 6 compressors
Supply:
400 V 3-phase

Construction

  • R290 propane refrigerant
  • Two circuits, four or six compressors
  • MWT option to -10°C outlet
  • Low-ambient option to -20°C
  • Max ambient 45°C

Ratings

  • Nominal kW
  • SEER 4.9 to 5.1
  • SEPR HT 6.4 to 6.5
  • Rating point not stated

Specifications sourced from ICS Cool Energy's published i-Chiller product pages and datasheets (icscoolenergy.com), October 2026. ICS Cool Energy and i-Chiller are trademarks of their owner; referenced here for cross-reference only. Capacities are ICS's nominal figures in kW, converted at 3.517 kW per ton. Confirm against the unit nameplate before ordering.

i-Chiller Process Max n, 165 to 242 kW

Propane at Plant Scale

Three models on the product page. The IC050n at 164.9 kW, IC060n at 206 kW and IC070n at 241.5 kW nominal; the 2024 datasheet covers larger IC075in to IC150in models, 245 to 472 kW.

Seasonal efficiency is published. SEER 4.9 to 5.1 and SEPR HT 6.4 to 6.5.

Two circuits. Four compressors on the IC050n and six on the IC060n and IC070n.

Options. A medium water temperature version to -10°C outlet and a low-ambient option to -20°C, with a maximum ambient of 45°C. An MWT unit set below about -7°C (20°F) is past the low end of the Temptek range, and its match is worked out on request rather than taken from these pages.



calipers measuring a steel plate on a workbench

Two R290 circuits with four or six compressors in a 2,232 mm wide frame.

Request a Quote

i-Chiller Process Max n Series Applications

Low-GWP duty
Low-GWP duty
Plant chilled water
Plant chilled water
Plant-wide molding
Plant-wide molding
Outdoor pads
Outdoor pads

schematic of the i-Chiller Process Max n series circuit, showing where the process fluid and the condenser heat go

Propane Changes the Site Rules

R290 is highly flammable, A3, and a propane chiller of this size carries its own siting and ventilation rules. A Temptek replacement on conventional refrigerant changes those again; settle the location before the swap.

Every part-number page below names the Temptek unit we supply in its place, sized from ICS's nominal kW on Temptek's 0.80 multiplier at 40°F, which covers a 12/7°C rating, and built for North American supply rather than 400 V / 50 Hz.
Call and talk it through with an engineer: 1-805-484-2992

Propane Process Max n: Before the Swap

Because both of the smaller models fit under the TTOACS-80D-MZC-2P's 75.8 tons once divided by 0.80, and the IC070n does not. The IC050n's 164.9 kW calls for 58.61 tons and the IC060n's 206 kW for 73.21, but the IC070n's 241.5 kW, about 68.67 tons, calls for 85.84 and goes to the TTOACS-120D-MZC-2P at 110.1 tons. The IC060n is the tight one, with about 2.6 tons in hand. If an IC060n runs near full load at a set point below 7°C, or its pad sees a hot summer, give us those conditions so the margin is checked before the order.

Check the model code: the three on these pages are the IC050n, IC060n and IC070n, while ICS's 2024 datasheet adds IC075in to IC150in models from 245 to 472 kW. Those larger units are worked from their own nameplate kW in the same way. At 245 kW, about 69.66 tons, the call is 87.1 tons after the multiplier; at 472 kW, about 134.2 tons, it is 167.8. Send the code and the kW on the plate and the cross-reference is made from that figure.

Two things: who recovers the propane charge, and where the replacement will stand. A propane charge at this scale needs a contractor equipped for A3 refrigerant, and the approvals for the present location were written around R290. The Temptek unit uses a conventional refrigerant, so a site that chose propane to meet a low-GWP policy should raise that before the selection is fixed, not at handover. Decide whether the new chiller goes on the same pad and keeps its clearances, and line up the electrical change away from 400 V three-phase at the same time.