| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Portable Chiller | Air-Cooled | 36.75 Tons @ 50°F | Not published |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n AD-40 as shown on this page.
The Mokon AD-40 is a 36.75-ton air-cooled dual-circuit portable chiller from the Iceman Dual Circuit line. Mokon publishes 441,000 Btu/h, 36.75 tons, at 50°F leaving fluid, 90°F ambient and 2.4 GPM per ton. Its range is 20 to 65°F leaving fluid, with a 7-1/2 hp process pump and a 100-gallon tank. It has two refrigerant circuits on tandem scroll compressors, which Mokon says turn down to 10% of overall capacity. Replacement: we supply the Temptek TTI-40A, an air-cooled central chiller rated 40 tons at 50°F, against the 36.75 tons Mokon publishes for this unit at 50°F leaving fluid and 90°F ambient. Temptek rates at 95°F ambient, five degrees hotter than Mokon's 90°F, so a Temptek unit that covers the Mokon figure keeps a margin. It is a central chiller rather than a portable, because the largest Temptek air-cooled portable falls short of this figure.
Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.