| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Outdoor Chiller | Outdoor Air-Cooled | 21.91 Tons @ 50°F | Not published |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n OA-25 as shown on this page.
The Mokon OA-25 is a 21.91-ton outdoor air-cooled chiller from the Iceman OA line, with its pump and reservoir on board. Mokon publishes 262,870 Btu/h, 21.91 tons, at 50°F leaving fluid, 2.4 GPM per ton and 90°F ambient, on 30% ethylene glycol. It runs 20 to 65°F leaving fluid in -20 to 95°F outdoor ambient, with a 5 hp pump and a 100-gallon reservoir. Replacement: we supply the Temptek TTOACS-25S-CG-1P, an outdoor air-cooled packaged chiller rated 24.2 tons at 50°F, against the 21.91 tons Mokon publishes for this unit at 50°F leaving fluid and 90°F ambient on 30% ethylene glycol. Mokon rates the OA on 30% ethylene glycol; the Temptek figure is on water and falls on glycol, so we confirm the size with your glycol mix before quoting. Temptek's 95°F ambient rating is the hotter of the two.
Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.