| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Portable Chiller | Air-Cooled | 2.81 Tons @ 50°F | R-454B |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n AS-3 as shown on this page.
The Mokon AS-3 is a 2.81-ton air-cooled single-circuit portable chiller from the Iceman SC line. Mokon publishes 33,720 Btu/h, 2.81 tons, at 50°F leaving fluid, 90°F ambient and 2.4 GPM per ton. It runs 20 to 65°F leaving fluid on R-454B, with a 1 hp process pump, a 15-gallon tank and 1 in FNPT process connections. Replacement: we supply the Temptek CG-3A, an air-cooled portable chiller rated 2.9 tons at 50°F, against the 2.81 tons Mokon publishes for this unit at 50°F leaving fluid and 90°F ambient. Temptek rates at 95°F ambient, five degrees hotter than Mokon's 90°F, so a Temptek unit that covers the Mokon figure keeps a margin.
Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.