1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the Mokon Iceman SC Series

Iceman SC Series

Mokon's main portable line: single-circuit Iceman SC chillers in air-cooled and water-cooled pairs, from 9,684 to 575,760 Btu/h.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Single-Circuit Portable 1 to 48 Tons 22

Specifications


Configuration & Size

Capacity:
9,684 to 575,760 Btu/h
Models:
22 part numbers
Leaving Fluid:
10 to 65°F from 5 tons
Process Pump:
1 to 7-1/2 hp
Refrigerant:
R-454B (A2L)

Construction

  • Scroll compressors (1-ton reciprocating)
  • Stainless brazed plate evaporator
  • Stainless centrifugal pump, TEFC motor
  • Insulated plastic tank, 10 to 150 gal
  • Hot gas bypass, 1/16 DIN controller

Ratings

  • Rated at 50°F leaving fluid
  • 90°F ambient, 2.4 GPM/ton
  • 85°F condensing water, 3 GPM/ton
  • R-454B; R-513A on 1 ton

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.

Iceman SC Series, 1 to 48 Tons

Eleven Sizes, Two Condensers

Twenty-two part numbers in eleven pairs. Each size comes as an air-cooled AS (or AC) model and a water-cooled WS (or WC) model with the same published capacity, from 9,684 Btu/h on the AC-1 to 575,760 Btu/h on the AS-50.

Rated at 50°F and 2.4 GPM per ton, against 90°F ambient air for the air-cooled units and 85°F condensing water at 3 GPM per ton for the water-cooled ones. The AS-15 is listed at 175,080 Btu/h, 14.6 tons.

The low end of the range depends on size. The 1-ton unit runs 20 to 60°F on R-513A and a reciprocating compressor; the 2 and 3-ton units 20 to 65°F; everything from 5 tons up 10 to 65°F on scroll compressors and R-454B, an A2L refrigerant. The part-number matches hold from 20°F up; an SC set between 10 and 19°F is colder than the Temptek line goes, so tell us the setpoint and it is rated on its own.

Tanks and pumps grow in steps. From a 10-gallon tank and 1 hp pump on the 1-ton unit to 150 gallons and 7-1/2 hp on the 50-ton. Mokon publishes no dimensions for the 30 to 50-ton sizes.



a cluster of industrial pressure gauges on process piping

Scroll compressor, brazed plate evaporator, insulated tank and a stainless pump on casters.

Request a Quote

Iceman SC Series Applications

Plastics molding
Plastics molding
Machine tools
Machine tools
Brewery glycol
Brewery glycol
Chemical process
Chemical process

schematic of the Iceman SC series circuit, showing where the process fluid and the condenser heat go

A2L Refrigerant Changes the Room

From 2 tons up the Iceman SC runs on R-454B, which is classed A2L, mildly flammable. That brings its own rules for the room the chiller sits in, its ventilation and its service, and it is worth checking before a unit is moved into a small mechanical space.

An air-cooled portable also puts its condenser heat, about the load plus compressor work, into the room. The indoor vs outdoor installation guide covers when the chiller belongs outside.

Every part-number page below names the Temptek unit we supply in its place, a Temptek CG portable of the same condenser type, sized to cover the published 50°F capacity; where the largest Temptek portable falls short, a Temptek TTI central chiller.
Call and talk it through with an engineer: 1-805-484-2992

What Engineers Ask About the Iceman SC Line

Every size from 5 tons up: those units are listed down to 10°F leaving fluid, while the Temptek line stops at 20°F. The 1-ton unit and the 2 and 3-ton units bottom out at 20°F, so they stay within reach. If an AS-5, WS-5 or larger is set between 10 and 19°F, the named CG or TTI pick does not apply at that set point, and the duty goes to an application specialist. At 20°F and above the pick still has to be confirmed at the set point, since the part-number pages match on the 50°F figure and a chiller makes much less in the 20s.

Only with ventilation sized for it, because an AS-15 at full load rejects its 175,080 Btu/h of process heat, 14.6 tons, plus the compressor's own heat into that room. Without make-up air and exhaust to match, the room temperature climbs untill the chiller's capacity falls with it, usually on the day the load is highest. In a small room the R-454B adds its A2L rules on top. If the room cannot shed that heat, a water-cooled unit on tower water or a unit outside is the better arrangement, so tell us where the condenser air goes today.

Measure the unit you have and every door, aisle and turn on the way in, since Mokon gives only shipping weights for the 30 to 50-ton sizes. Those are about 3,860 lbs for the AS-30, 4,995 lbs for the WS-40 and 5,495 lbs for the AS-50. Both the AS-30 and AS-50 are replaced by a Temptek TTI central chiller, so the new unit may be rigged and set in place rather than rolled in on casters. Check the floor rating where it will stand as well.

Close, and closest on the water-cooled side: the WS-7.5, at 7.41 tons, goes to the CG-7.5W rated 7.6 tons, a margin of about 0.19 tons. On the air-cooled side the AS-2, at 2.08 tons, goes to the CG-3A rated 2.9 tons. Air-cooled Temptek units are rated at 95°F ambient against Mokon's 90°F, which adds a cushion the numbers do not show. Water-cooled units compare directly at 50°F leaving fluid, so a WS-7.5 on warm tower water or at a colder set point is the one to confirm first.

The glycol set point, the mix and the crash load, because the published figures are at 50°F and a brewery glycol loop runs well below that. At 2.4 GPM per ton the rating assumes a 10°F rise on water; glycol carries less heat per gallon, so the same flow gives a wider rise. Work the crash load from the fermenter volume in barrels, at 31 gallons each, how many degrees it must drop and in how many hours. Give us the number of tanks crashing at once too, since that overlap is the peak the chiller has to meet.

Quote Request Form:

Questions?

1-805-484-2992