1-805-484-2992

Quotes - Sizing - Sales

ASM-10

Mokon
Product Type Capacity Refrigerant
Portable Chiller Air-Cooled 9.62 Tons @ 50°F Not published

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ASM-10 as shown on this page.

Replacement chiller for the Mokon ASM-10

Description

The Mokon ASM-10 is a 9.62-ton air-cooled modulating portable chiller from the Iceman SM line. Mokon publishes 115,400 Btu/h, 9.62 tons, at 50°F leaving fluid, 90°F ambient and 2.4 GPM per ton. Its range is 20 to 65°F leaving fluid, with a 1-1/2 hp process pump and a 20-gallon tank. Its digital scroll compressor varies output from 10% to 100% by unloading rather than hot gas bypass. Replacement: we supply the Temptek CGD-10A, an air-cooled portable chiller rated 9.8 tons at 50°F, against the 9.62 tons Mokon publishes for this unit at 50°F leaving fluid and 90°F ambient. Temptek rates at 95°F ambient, five degrees hotter than Mokon's 90°F, so a Temptek unit that covers the Mokon figure keeps a margin.

Product Overview

Part Number:
ASM-10
Manufacturer:
Mokon
Replacement Unit:
Temptek CGD-10A

Published Capacity

Cooling Capacity:
115,400 Btu/h (9.62 tons)
Rating Point:
50°F leaving fluid, 90°F ambient, 2.4 GPM/ton
Leaving Fluid Range:
20 to 65°F

Configuration & Specifications

Condenser:
Air-cooled
Compressor:
Digital scroll
Circuits:
Single
Refrigerant:
Not published

Pump & Reservoir

Process Pump:
1-1/2 hp
Flow Rate (min / max):
24 / 35 GPM
Nominal Pressure:
Up to 37 PSI
Tank Size:
20 gallons

Connections

Process Connections:
1-1/2 in FNPT

Dimensions & Weight

Dimensions (L x W x H):
58 x 37 x 45 in, approximate
Shipping Weight:
960 lbs, approximate

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.