Replacement unit for the Mokon Iceman SM Series

Iceman SM Series

Mokon's modulating portable: a digital scroll compressor that follows the load from 10 to 100%, 5 to 15 tons.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Modulating Portable 5 to 15 Tons 6

Specifications


Configuration & Size

Capacity:
58,300 to 173,800 Btu/h
Models:
6 part numbers
Modulation:
10 to 100%
Process Pump:
1 to 3 hp
Leaving Fluid:
20 to 65°F

Construction

  • Digital scroll compressor
  • Electronic expansion valve
  • Stainless brazed plate evaporator
  • Stainless centrifugal pump
  • 1/8 DIN controller

Ratings

  • Rated at 50°F leaving fluid
  • 90°F ambient, 2.4 GPM/ton
  • 85°F condensing water, 3 GPM/ton
  • 20 to 65°F range

Specifications sourced from Mokon's published chiller product pages and series datasheets (mokon.com), October 2026. Mokon, Iceman, Full Range, Pura-Therm and Xtreme-Therm are trademarks of their owner; referenced here for cross-reference only. Mokon notes its technical data is subject to change without notice. Confirm against the unit nameplate before ordering.

Iceman SM Series, 5 to 15 Tons

Capacity That Follows the Load

Six part numbers in three pairs. The ASM-5, ASM-10 and ASM-15 are air-cooled and the WSM-5, WSM-10 and WSM-15 water-cooled, from 58,300 to 173,800 Btu/h at 50°F leaving fluid.

The compressor unloads itself. Mokon describes a digital scroll that alternates between a loaded phase at full capacity and an unloaded phase with little or no output, for 10 to 100% capacity, rather than throwing the extra away through hot gas bypass.

The rest is standard Iceman. Stainless brazed plate evaporator, stainless centrifugal pump of 1 to 3 hp, insulated plastic tank, and an electronic expansion valve.

The range is 20 to 65°F. Mokon lists ranges up to 75°F as an option.



heavily insulated refrigeration piping in a plant

Digital scroll compressor with an electronic expansion valve, tank and pump in one portable frame.

Request a Quote

Iceman SM Series Applications

Variable loads
Variable loads
Plastics molding
Plastics molding
Lasers and optics
Lasers and optics
Machine tools
Machine tools

schematic of the Iceman SM series circuit, showing where the process fluid and the condenser heat go

Where Modulation Pays

A fixed-speed chiller on a load that swings holds temperature by cycling or by bypassing hot gas, and either costs energy and stability. A modulating unit earns its keep where the load moves through the day: a molding cell that changes jobs, a process that idles between batches.

On a steady full load the diffrence is small, and the replacement can be chosen on tons alone. The glycol chiller sizing guide helps tell which you have.

Every part-number page below names the Temptek unit we supply in its place, a Temptek CG portable of the same condenser type, sized to cover the published 50°F capacity.
Call and talk it through with an engineer: 1-805-484-2992

Iceman SM: When Modulation Matters in a Swap

Do not assume it: the CG portables are matched to the SM on condenser type and published 50°F capacity, not on the digital scroll. If the process depends on smooth 10 to 100% capacity, say so, along with the lowest load it runs at. On an ASM-10, 10% of 9.62 tons is just under one ton, about 0.96, and a load that sits near that for hours is where a fixed-capacity replacement behaves differently. With that figure the selection can be checked at the low end, not only at peak.

The ASM-5: it is published at 4.86 tons and the CGD-5A is rated 4.9, a margin of only 0.04 tons. The ASM-10 at 9.62 tons against the CGD-10A's 9.8 leaves 0.18, and the ASM-15 at 14.07 against the CG-15AF's 14.5 leaves 0.43. Those are all 50°F figures. At a colder set point, in a hotter room or on a load that has grown, the ASM-5 pick is the first to run short, so it is the one to confirm at your conditions. The water-cooled WSM-5, WSM-10 and WSM-15 map to the CGD-5W, CGD-10W and CGD-15W.

Yes, but at the actual set point, since the published 50°F capacity says little about a unit running at 70°F. A warmer set point raises what any chiller makes, so the 50°F match usually covers it on capacity; the real check is that the replacement's control range reaches your set point. Tell us wether your SM carries the extended range and what it is set to.