1-805-484-2992

Quotes - Sizing - Sales

ASC075X

Multistack
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 73 Tons nominal R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ASC075X as shown on this page.

Replacement chiller for the Multistack ASC075X

Description

The Multistack ASC075X is an ASC air-cooled stand-alone chiller with 6 scroll compressors totalling 73 nominal tons, dual refrigeration circuits on R-410A and a brazed plate evaporator. It has 4 condenser fans moving 54,000 cfm and weighs 5,120 lb operating. At 460 V the catalog lists 137 A minimum circuit ampacity and 175 A maximum overcurrent protection. Replacement: we supply the Temptek TTOACS-120D-MZC-2P, an outdoor air-cooled packaged chiller rated 110.1 tons at 50°F, against the 73 tons Multistack publishes for this unit at its total nominal tons (AHRI 550/590). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.

Product Overview

Part Number:
ASC075X
Manufacturer:
Multistack
Series:
ASC Series
Replacement Unit:
Temptek TTOACS-120D-MZC-2P

Published Capacity

Total Nominal Capacity:
73 tons
Rating Basis:
AHRI Standard 550/590 (guide specification)
Low Ambient Option:
To -20°F

Configuration & Specifications

Compressors:
6 scroll
Refrigeration Circuits:
Dual
Refrigerant:
R-410A
Evaporator:
Brazed plate
Evaporator Water Volume:
9 gallons
Condenser Fans:
4
Total Airflow:
54,000 cfm
Controller:
Carel c.pCO

Electrical (MCA / MOP)

208 V / 3 ph / 60 Hz:
310/400 A
230 V / 3 ph / 60 Hz:
274/350 A
460 V / 3 ph / 60 Hz:
137/175 A
575 V / 3 ph / 60 Hz:
120/150 A

Connections

Chilled Water Connections:
3 in grooved

Dimensions & Weight

Length (X):
115 in
Width (Y):
79 in
Height (Z):
112 in
Shipping Weight:
5,045 lb
Operating Weight:
5,120 lb

Specifications sourced from Multistack's published ASC air-cooled stand-alone chiller product catalog (multistack.com), October 2026. Multistack is a trademark of its owner; referenced here for cross-reference only. Capacities are the catalog's total nominal tons. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales