ASC Series

Multistack's packaged air-cooled chiller: the ASC, 26 models from 19 to 198 nominal tons with dual circuits on R-410A.

PRODUCT TYPE CAPACITY MODELS
Air-Cooled Scroll Chiller Packaged, Air-Cooled 19 to 198 nominal tons 26

Specifications


Configuration & Size

Capacity:
19 to 198 nominal tons
Models:
26 part numbers
Refrigerant:
R-410A
Circuits:
Dual
Supply:
208, 230, 460 or 575 V, 3 ph

Construction

  • Two to six scroll compressors
  • Dual refrigeration circuits
  • Brazed plate evaporator
  • Tube and fin condenser, low-sound fans
  • Carel c.pCO controller with WiFi

Ratings

  • Total nominal tons
  • AHRI 550/590 per guide specification
  • Low ambient option to -20°F
  • 64 to 78 dBA at 30 feet

Specifications sourced from Multistack's published ASC air-cooled stand-alone chiller product catalog (multistack.com), October 2026. Multistack is a trademark of its owner; referenced here for cross-reference only. Capacities are the catalog's total nominal tons. Confirm against the unit nameplate before ordering.

ASC, 19 to 198 Nominal Tons

One Package, Two Circuits

Twenty-six models. From the ASC021X at 19 nominal tons to the ASC195X at 198, each with two to six scroll compressors.

Two frame families. The 020X to 041X are 77 inches long and about 96 high; the 050X to 195X are 79 inches wide, 112 high and 115 to 343 long.

Electrical data for every voltage. The catalog lists MCA and MOP at 208, 230, 460 and 575 V: an ASC060X draws 120 A MCA at 460 V.

Options. Pumps, an expansion tank, glycol feeders, desuperheaters, hot gas bypass and ECM fans are offered on select sizes.



a filling nozzle depositing stew into cups on a packing line

Scroll compressors on dual R-410A circuits, a brazed plate evaporator and tube and fin condenser coils.

Request a Quote

ASC Series Applications

Chilled water
Chilled water
Process loops
Process loops
Plastics molding
Plastics molding
Outdoor pads
Outdoor pads

schematic of the ASC series circuit, showing where the process fluid and the condenser heat go

Nominal Tons Are a Starting Point

The ASC catalog gives total nominal tons, the sum of the compressor sizes, under an AHRI 550/590 rating. At a colder glycol set point the working capacity is lower. The leaving fluid temperature guide shows how much, and the glycol chiller sizing guide works the load itself.

Every part-number page below names the Temptek unit we supply in its place, sized from Multistack's nominal tons on Temptek's 0.80 multiplier at 40°F, or points to the add-on module range where the size is past a single chiller.
Call and talk it through with an engineer: 1-805-484-2992

Multistack ASC: Nominal Tons and What Replaces Them

Because the model number is a size label, while the catalog figure is total nominal tons from the compressors fitted, and the two do not always agree. The ASC150X lists 140 tons, the ASC060X 57 tons from four scroll compressors and the ASC195X 198, so the badge can sit above or below the true figure, by as much as 10 tons in this range. Size from the tons column, not the digits. On the Temptek match, the true 140 calls for 175 tons of 50°F rating and the badge reading 187.5. Both land on the TTOACS-210D-MZC-2P at 188 tons, but the badge makes a 13-ton margin look like half a ton, which misstates how much room is left for a colder set point.

More than twice the current of the same chiller at 460 V, so the existing feeder, not the chiller, often sets what can go back on the pad. The catalog lists the ASC060X at 263 A MCA and 350 A MOP on 208 V, against 120 A and 150 A on 460 V, 232 A and 300 A on 230 V, and 98 A and 125 A on 575 V. If the plant moves the supply to a higher voltage during the swap, the conductors can shrink; if it stays on 208 V, the new unit has to suit a feeder already built for over 260 A. Give us the nameplate voltage, breaker size and conductor size with the model number, and the selection is checked against all three.

Anything that served the plant rather then the chiller. A desuperheater means the ASC was heating water somewhere, and that heat stops when the unit leaves unless the duty is replaced. Factory pumps and an expansion tank mean the loop loses circulation and expansion volume with the cabinet. A glycol feeder was holding the mix, so plan another way to make up fluid. Hot gas bypass points to a light-load problem the old unit was covering. These were offered on select sizes only, so check the nameplate and the piping and list what you find on the request.

About 247.5 tons of Temptek 50°F rating: the ASC195X's 198 nominal tons divided by the 0.80 multiplier, which no single Temptek outdoor chiller makes, so add-on chiller modules are paired to the load. Lower in the range the picture changes. The 140-ton ASC150X calls for 175 tons and the TTOACS-210D-MZC-2P makes 188, so one outdoor package covers it with 13 tons spare. At the small end the 20-ton ASC020X asks for 25 tons, covered by the TTOACS-30S-CG-1P at 28.8. A module set will not sit where the 343-inch, 12,430 lb ASC195X did without a new layout, so send the pad plan and pipe entry points.