M5E1008B22R405-A-V

PRO Refrigeration
Product Type Capacity Refrigerant
Glycol Chiller Air-Cooled Packaged 0.55 Tons @ 35°F R448 / R449

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n M5E1008B22R405-A-V as shown on this page.

Replacement chiller for the PRO Refrigeration M5E1008B22R405-A-V

Description

The PRO M5E1008B22R405-A-V is a 0.75 hp low-temperature glycol chiller from PRO's legacy M5 line, for chilled fluid down to -5°F, indoors or outdoors. PRO publishes capacity at 90°F air: 2,920 Btu/h at -5°F, 3,690 Btu/h at 5°F, 4,590 Btu/h at 15°F, 5,590 Btu/h at 25°F, 6,650 Btu/h at 35°F, 7,210 Btu/h at 45°F leaving fluid. It carries a 5-gallon tank and a pump rated 6 GPM at 23 ft of head, on R448/R449. Replacement: we supply the Temptek CF-1A, a fractional-ton portable chiller rated 1 ton at 50°F, against the 0.55 tons PRO Refrigeration publishes for this unit at 35°F leaving glycol and 90°F ambient. PRO publishes no 50°F or usable 30°F figure here, so its 35°F figure is matched on Temptek's 30°F multiplier of 0.60; Temptek makes more than that at 35°F, so the pick keeps a margin. We confirm it at your set point. Divided by 0.60, the 0.55 tons call for at least 0.92 tons of Temptek 50°F rating.

Product Overview

Part Number:
M5E1008B22R405-A-V
Manufacturer:
PRO Refrigeration
Series:
M5 Series
Replacement Unit:
Temptek CF-1A

Published Capacity

Capacity at -5°F, 90°F Air:
2,920 Btu/h (0.24 tons)
Capacity at 5°F, 90°F Air:
3,690 Btu/h (0.31 tons)
Capacity at 15°F, 90°F Air:
4,590 Btu/h (0.38 tons)
Capacity at 25°F, 90°F Air:
5,590 Btu/h (0.47 tons)
Capacity at 35°F, 90°F Air:
6,650 Btu/h (0.55 tons)
Capacity at 45°F, 90°F Air:
7,210 Btu/h (0.6 tons)
Temperature Range:
-5 to 45°F

Configuration & Specifications

Horsepower:
0.75 HP
Refrigerant:
R448 / R449
Condenser Air Flow:
680 CFM
Sound Level:
66 dB

Pump & Reservoir

  • Pump: 6 GPM at 23 ft TDH
  • Tank: 5 gallons

Electrical

  • MCA / MOP at 115/1: 25/30 A
  • MCA / MOP at 230/1: 15/15 A

Connections

Fluid Connections:
1 in MNPT

Dimensions & Weight

Dimensions (L x W x H):
33 x 30 x 27 in
Shipping Weight:
400 lbs
Operating Weight:
400 lbs

Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales