| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| CO2 Glycol Chiller | CO2 Packaged | 65.95 Tons @ 30°F | R744 (CO2) |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PG-100VA750-TC-XX as shown on this page.
The PRO PG-100VA750-TC-XX is a CO2 (R744) glycol chiller from the PROGreen line, on 100 (2 x 50 HP Bitzer R744) compressors with a 750-gallon dual-chamber coolant vessel and onboard heat recovery to 180°F potable water. PRO publishes a capacity table by ambient; at 90°F ambient it lists 654,545 Btu/h at 20°F, 720,718 Btu/h at 25°F, 791,373 Btu/h at 30°F coolant temperature. Above about 75°F ambient the CO2 system runs transcritical, and PRO's capacity falls steadily with ambient. Replacement: we supply the Temptek TTOACS-120D-MZC-2P, an outdoor air-cooled packaged chiller rated 110.1 tons at 50°F, against the 65.95 tons PRO Refrigeration publishes for this unit at 30°F leaving glycol and 90°F ambient. PRO publishes no 50°F rating. Temptek's published capacity multiplier at a 30°F set point is 0.60 of its 50°F rating, so the pick is sized at PRO's 30°F figure divided by 0.60, and confirmed at your set point before quoting. Divided by 0.60, the 65.95 tons call for at least 109.92 tons of Temptek 50°F rating.
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.