| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Air-Cooled Packaged | 52.33 Tons @ 30°F | R448A/R449A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PB240B114R8550-V-V as shown on this page.
The PRO PB240B114R8550-V-V is a packaged semi-hermetic glycol chiller from PRO Refrigeration's V Piston line, with a 40 hp compressor rating on the data sheet and a 550-gallon tank. PRO publishes estimated capacity at 90°F ambient: 488,000 Btu/h at 20°F, 556,000 Btu/h at 25°F, 628,000 Btu/h at 30°F, 708,000 Btu/h at 35°F leaving glycol. Bitzer semi-hermetic compressors, per PRO's specification. Dual stainless steel centrifugal pump configuration with dedicated process and internal circulation pump. Replacement: we supply the Temptek TTOACS-120D-MZC-2P, an outdoor air-cooled packaged chiller rated 110.1 tons at 50°F, against the 52.33 tons PRO Refrigeration publishes for this unit at 30°F leaving glycol and 90°F ambient. PRO publishes no 50°F rating. Temptek's published capacity multiplier at a 30°F set point is 0.60 of its 50°F rating, so the pick is sized at PRO's 30°F figure divided by 0.60, and confirmed at your set point before quoting. Divided by 0.60, the 52.33 tons call for at least 87.22 tons of Temptek 50°F rating.
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.