1-805-484-2992

Quotes - Sizing - Sales

PB2110B162R42000-V-VD

PRO Refrigeration
Product Type Capacity Refrigerant
Glycol Chiller Air-Cooled Packaged 146.83 Tons @ 30°F R448A/R449A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PB2110B162R42000-V-VD as shown on this page.

Replacement chiller for the PRO Refrigeration PB2110B162R42000-V-VD

Description

The PRO PB2110B162R42000-V-VD is a screw glycol chiller from PRO Refrigeration's V-Screw line, with a 110 hp compressor rating on the data sheet and a 2000-gallon tank. PRO publishes estimated capacity at 90°F ambient: 1,398,000 Btu/h at 20°F, 1,572,000 Btu/h at 25°F, 1,762,000 Btu/h at 30°F, 1,970,000 Btu/h at 35°F leaving glycol. Bitzer semi-hermetic screw compressors, per PRO's specification. Dual stainless steel centrifugal pump configuration with dedicated process and internal circulation pump. Replacement: no single Temptek unit reaches 244.72 tons, so we supply it from our sister line: add-on chiller modules for plant-wide systems to 300 tons, paired to the load.

Product Overview

Part Number:
PB2110B162R42000-V-VD
Manufacturer:
PRO Refrigeration
Series:
V-Screw Series

Published Capacity

Capacity at 20°F, 90°F Ambient:
1,398,000 Btu/h (116.5 tons)
Capacity at 25°F, 90°F Ambient:
1,572,000 Btu/h (131 tons)
Capacity at 30°F, 90°F Ambient:
1,762,000 Btu/h (146.83 tons)
Capacity at 35°F, 90°F Ambient:
1,970,000 Btu/h (164.17 tons)
Capacity at 25°F, 100°F Ambient:
65,600 Btu/h
Capacity at 30°F, 100°F Ambient:
72,200 Btu/h
Capacity at 35°F, 100°F Ambient:
79,200 Btu/h

Configuration & Specifications

Compressor (data sheet):
110 HP
Condenser:
Air Cooled
Refrigerant:
R448A/R449A
Evaporator:
Brazed Plate
Controls:
Microprocessor
Electrical Enclosure:
NEMA 4
Sound Level:
87 dB at 1 m

Pump & Reservoir

  • Circulation Pump: 10 HP
  • Process Pump: 15 HP
  • Tank: 2000 gallons

Electrical

  • MCA / MOP at 460/3/60: 517 / 702 A

Connections

Glycol Connections:
4 in Flange
Expansion Fittings:
4 ea 3 in

Dimensions & Weight

Dimensions:
442 inL x 98 inW x 119 inH
Shipping Weight:
21000 lbs
Operating Weight:
39000 lbs

Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales