| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Glycol Chiller | Air-Cooled Packaged | 16.65 Tons @ 30°F | Not published |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PS210B98R4200-V-V as shown on this page.
The PRO PS210B98R4200-V-V is a 20 hp scroll glycol chiller from PRO's legacy V-Scroll line, on two compressors of 10 hp each. PRO's legacy table lists estimated capacity at 90°F ambient: 160,600 Btu/h at 20°F, 179,400 Btu/h at 25°F, 199,800 Btu/h at 30°F, 222,200 Btu/h at 35°F leaving fluid. It carries a 200-gallon tank with separate circulation and process pumps. Replacement: we supply the Temptek TTOACS-30S-CG-1P, an outdoor air-cooled packaged chiller rated 28.8 tons at 50°F, against the 16.65 tons PRO Refrigeration publishes for this unit at 30°F leaving glycol and 90°F ambient. PRO publishes no 50°F rating. Temptek's published capacity multiplier at a 30°F set point is 0.60 of its 50°F rating, so the pick is sized at PRO's 30°F figure divided by 0.60, and confirmed at your set point before quoting. Divided by 0.60, the 16.65 tons call for at least 27.75 tons of Temptek 50°F rating.
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.