PRO's legacy dual-scroll chillers: 20 and 30 hp on two compressors, with a 200-gallon tank and separate pumps.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Glycol Chiller | Scroll, Legacy | 20 and 30 HP | 2 |
Specifications sourced from PRO Refrigeration's published chiller data sheets, series one-sheets and legacy specification tables (prochiller.com), October 2026. PRO Refrigeration, PRO Chiller Systems, Chill&Flow, ChilStar, PRO4, V Piston, V-Scroll, Revolution, PROGreen and PROElliot are trademarks of their owner; referenced here for cross-reference only. PRO publishes these as estimated capacities. Confirm against the unit nameplate before ordering.
Two models. The PS210B98R4200-V-V on two 10 hp compressors and the PS215B98R4200-V-V on two 15 hp.
Capacity at the glycol temperature. The PS215 is listed at 297,400 Btu/h at 30°F and 331,200 at 35°F, at 90°F ambient; the PS210 at 199,800 and 222,200.
Separate pumps. One 2 hp circulation pump and one 2 hp process pump, on a 200-gallon tank with a 2-inch glycol connection.
The same frame. Both in a 114 x 57 x 100-inch coated steel frame with galvanized housing, about 5,000 lbs operating.
Two scroll compressors, a 200-gallon tank and separate circulation and process pumps.
Request a Quote
PRO still publishes the V-Scroll table on its Legacy Chillers page, and the figures here are read from it. The refrigerant is not listed; check the nameplate.
Every part-number page below names the Temptek unit we supply in its place, sized from PRO's 30°F figure on Temptek's published multiplier: a Temptek unit makes 0.60 of its 50°F rating at a 30°F set point, so the pick is the PRO figure divided by 0.60.