Description
The Temptek CG-20A-RC is a indoor chiller with a remote air-cooled condenser rated 18.5 tons at 50°F leaving fluid and 115°F condensing temperature. It runs a 20 HP tandem scroll compressor on R-454B. The process pump delivers 48 GPM at 43 PSI (3 HP) from a 65 gallons reservoir. It is paired with the KCL-32-KR remote air-cooled condenser (2 fans). Below a 48°F setpoint the loop needs glycol, and capacity falls below the 50°F rating. Also available: the alternate MG-20ARC, the same indoor remote-condenser format and capacity class.
Product Overview
Part Number:
CG-20A-RC
Manufacturer:
Temptek
Configuration & Specifications
Capacity (Tons):
18.5
Capacity (kW):
64.9
Compressor HP:
20
Compressor Quantity:
1
Compressor Type:
Tandem Scroll
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 3
- Process Pump GPM: 48
- Process Pump PSI: 43
- Process Pump Type: Centrifugal
- Reservoir: 65 gallons
- Reservoir Construction: Standard
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 76 (230V) / 38 (460V) / 31 (575V)
Remote Condenser
Circuits Served:
1
Fans:
2
Fan RPM:
1,140
Hot Gas Connection:
2-1/8"
Liquid Connection:
1-5/8"
Fan Motor Voltage:
460V
Fan Motor Phase:
Single Phase
Fan Motor Frequency:
60 Hz
Fan Motor Full Load Amps:
5.4
Tube Material:
Copper
Fin Material:
Aluminum
Coil Coating:
None
Fins Per Inch:
12
Height:
54"
Width:
44-5/8"
Depth:
112-1/2"
Shipping Weight:
740 lbs
Condenser Model:
KCL-32-KR
Connections, Dimensions & Weight
To Process Connection:
2"
From Process Connection:
2"
Water Make Up Connection:
1/2"
Height:
57"
Width:
34"
Depth:
80"
Shipping Weight:
1,900 lbs