Alternate unit for the Temptek CG-ARC Series

CG-ARC Series

The chiller stays inside next to the process; the condenser goes outside. Two refrigerant lines connect them.

PRODUCT TYPE CAPACITY MODELS
Indoor Chiller Remote Condenser 5 to 40 Tons 8

Specifications


Configuration & Size

Capacity:
4.9 to 36.7 tons
Models:
8 part numbers
Compressor:
Digital Scroll, Tandem Scroll
Process Flow:
12 to 92 GPM
Refrigerant:
R-454B

Construction

  • Indoor section: steel frame, stainless sheet metal
  • Remote condenser: galvanized steel cabinet
  • Copper tube, aluminum fin condenser coil
  • Centrifugal process pump
  • Polyethylene reservoir, auto make-up

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • Glycol required below 48°F
  • Power: 230/3/60, 460/3/60, 575/3/60

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

CG-ARC Indoor Chillers with Remote Condensers

Keep the Pump Inside, Put the Heat Outside

The CG-ARC is an indoor CG with the condenser moved outdoors. Eight models run from 4.9 to 36.7 tons. The indoor section carries the compressor, evaporator, tank and pump; the matched remote air-cooled condenser ships separately and is set on a pad or roof.

Each size is paired with a named condenser. The part-number pages list the condenser model, fan count, hot-gas and liquid line connections, weight and its own 460-volt single-phase fan load.

Why choose it over an air-cooled portable: none of the condenser heat enters the building, and the unit does not lose capacity when the plant floor gets hot. Why choose it over water-cooled: no tower or city water is needed.

Refrigerant is R-454B across the current range, rated at 50°F leaving water and 115°F condensing.



die casting machine with molten metal in a foundry

Process section indoors with tank and pump; the heat leaves through a remote condenser outdoors.

Request a Quote

CG-ARC Series Applications

Enclosed machining cells
Enclosed machining cells
Molding floors
Molding floors
Rooftop condenser installs
Rooftop condenser installs
Plants avoiding tower water
Plants avoiding tower water

schematic of the CG-ARC Series indoor chillers with remote air-cooled condensers circuit, showing where the process fluid and the condenser heat go

The Refrigerant Lines Are Part of the Selection

A remote-condenser chiller is field-piped refrigeration, and the piping is where these installations go wrong. Line length and the height difference between the chiller and the condenser set the line sizes, the oil-return arrangement and the refrigerant charge. A condenser mounted 30 feet above the chiller needs a different hot-gas riser than one at grade, and a run that doubles the listed length can starve the compressor of oil at low load.

On a replacement, the existing lines are rarely reusable as they stand. They may be sized for another refrigerant, and the current range runs R-454B, which is mildly flammable (A2L) and brings its own installation requirements. Give us the line length, the lift and a photo of the condenser nameplate, and the replacement arrives with the right condenser and the right line sizes.

More in remote condensers and piping.
Call and talk it through with an engineer: 1-805-484-2992

CG-ARC Remote Condensers: Installation Questions

The two-fan KCL-32-KR goes with the CG-20A-RC and the three-fan KCL-56-KR with the CG-40A-RC; the smallest size, the CGD-5A-RC, pairs with the single-fan KCS-008. Each condenser ships separately for setting on a pad or roof. Keep the pairing as listed: the condenser is matched to the compressor's heat rejection, and a different coil changes head pressure and capacity. The part-number page gives each condenser's dimensions and shipping weight for planning the pad or roof steel.

Three steps across the range: 1-1/8 inch hot gas and 7/8 inch liquid on the CGD-5A-RC, 2-1/8 and 1-5/8 inch on the CGD-15A-RC and CG-20A-RC, and 2-5/8 and 2-1/8 inch from the CG-25A-RC up. Those are the stub sizes at the units, not a line-size recommendation. A long horizontal run may call for a larger liquid line, and a condenser well above the chiller may need a smaller hot-gas riser to carry oil up at low load. Draw the route, with its length and the height difference, and we size the lines with the unit.

Because the condenser fan motors are listed at 460 V single-phase whatever the chiller's own supply. The chiller runs on 230, 460 or 575 V three-phase, and its condenser draws from 1.5 full-load amps on the single-fan KCS-008 to 8.5 amps on the three-fan units. A plant on 230 V or 575 V has to bring a 460 V single-phase feed to the pad or roof, or add a transformer for it, which is easy to miss when the electrical quote covers only the indoor section. Show both feeds on the drawing.

It raises the charge, because in a remote-condenser system the refrigerant charge grows with line lenght. R-454B is a mildly flammable A2L refrigerant, so a long run between the indoor section and the condenser puts more of it into the system, part of it inside the building, than a packaged unit holds. The installer has to follow the code requirements for A2L systems, including brazing practice and leak testing, and use components rated for the refrigerant. Setting the condenser as close to the indoor section as the site allows holds the charge down. Tell us the run length early so the charge can be estimated.

Not to plain water. The polyethylene reservoir carries an automatic make-up, and fed from a water line it tops the tank up with water every time the level drops, diluting the glycol a little with each leak or sample. On a loop below 48°F, where Temptek requires glycol, that dilution slowly raises the freeze point untill the evaporator is at risk. Either feed the make-up from a premixed glycol supply or isolate it and top up by hand, and test the mix on a schedule.