Description
The Temptek CG-15AFF is a air-cooled portable chiller rated 14.5 tons at 50°F leaving fluid and 115°F condensing temperature. It runs a 15 HP tandem scroll compressor on R-454B. The process pump delivers 36 GPM at 55 PSI (3 HP) from a 65 gallons reservoir. Below a 48°F setpoint the loop needs glycol, and capacity falls below the 50°F rating. Also available: the alternate MG-15AFF, the same air-cooled portable format and capacity class.
Product Overview
Part Number:
CG-15AFF
Manufacturer:
Temptek
Configuration & Specifications
Capacity (Tons):
14.5
Capacity (kW):
50.9
Compressor HP:
15
Compressor Quantity:
1
Compressor Type:
Tandem Scroll
Condenser Type:
Air-Cooled
Condenser Air Flow By:
Fan
Condenser Fan Quantity:
4
Condenser Fan HP:
3/4
Condenser CFM:
15,000
Design Ambient:
95°F
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 3
- Process Pump GPM: 36
- Process Pump PSI: 55
- Process Pump Type: Centrifugal
- Process Pump Construction: Stainless Steel
- Reservoir: 65 Gallons
- Reservoir Auto Make Up: Standard
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 94.0 (230V) / 47.0 (460V) / 39.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
2"
From Process Connection:
2"
Water Make-Up Connection:
1/2"
Height:
61"
Width:
68"
Depth:
64"
Shipping Weight:
2,200 LBS