| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Portable Chiller | Water-Cooled | 30 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n CG-30W as shown on this page.
The Temptek CG-30W is a water-cooled portable chiller rated 30 tons at 50°F leaving fluid and 105°F condensing temperature. It runs a 30 HP tandem scroll compressor on R-454B. The process pump delivers 72 GPM at 57 PSI (5 HP) from a 65 gallons reservoir. Condenser water is listed at 45 GPM of 60°F city water or 90 GPM of 85°F tower water. Below a 48°F setpoint the loop needs glycol, and capacity falls below the 50°F rating. Also available: the alternate MG-30W, the same water-cooled portable format and capacity class.