CGD-5W

Temptek
Product Type Capacity Refrigerant
Portable Chiller Water-Cooled 5.1 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n CGD-5W as shown on this page.

Chiller equivalent to Temptek CGD-5W

Description

The Temptek CGD-5W is a water-cooled portable chiller rated 5.1 tons at 50°F leaving fluid and 105°F condensing temperature. It runs a 5 HP digital scroll compressor on R-454B. The process pump delivers 12 GPM at 52 PSI (2 HP) from a 25 gallons reservoir. Condenser water is listed at 8 GPM of 60°F city water or 15 GPM of 85°F tower water. Below a 48°F setpoint the loop needs glycol, and capacity falls below the 50°F rating. Also available: the alternate MGD-5W, the same water-cooled portable format and capacity class.

Product Overview

Part Number:
CGD-5W
Manufacturer:
Temptek
Alternate Unit:
MGD-5W

Configuration & Specifications

Capacity (Tons):
5.1
Capacity (kW):
17.9
Compressor HP:
5
Compressor Quantity:
1
Compressor Type:
Digital Scroll
Condenser Type:
Water-Cooled
Condenser City Water:
8 GPM
Condenser Tower Water:
15 GPM
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 105°F condensing

Process Pump & Reservoir

  • Process Pump HP: 2
  • Process Pump GPM: 12
  • Process Pump PSI: 52
  • Process Pump Type: Centrifugal
  • Process Pump Construction: Stainless Steel
  • Reservoir: 25 Gallons
  • Reservoir Auto Make Up: Standard

Electrical

  • Voltage: 230V / 460V / 575V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Full Load Amps: 30.0 (230V) / 15.0 (460V) / 12.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
1-1/4"
From Process Connection:
1-1/4"
Water Make-Up Connection:
1/2"
Condenser Supply Connection:
1"
Condenser Drain Connection:
1"
Height:
40"
Width:
34"
Depth:
45"
Shipping Weight:
655 LBS