| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chilling Module | Remote Condenser | 180 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MA-180-RC-CCC as shown on this page.
The Temptek MA-180-RC-CCC is a chilling module with a remote air-cooled condenser rated 180 tons at 50°F leaving fluid and 115°F condensing temperature, on 3 refrigeration zones. It runs 6 scroll compressors of 30 HP each on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. It is paired with the KCL-95-KR remote air-cooled condenser (5 fans). At a glycol setpoint the published multipliers apply: about 144 tons at 40°F, 108 at 30°F and 72 at 20°F. Also available: the alternate CCC-180APT-RC, the same air-cooled chilling module format and capacity class.