1-805-484-2992

Quotes - Sizing - Sales
Alternate unit for the Temptek MA Series Chilling Modules

MA Series Chilling Modules

Refrigeration only: 5 to 180 tons of cooling for a plant that already has its tank, pumps and headers.

PRODUCT TYPE CAPACITY MODELS
Chilling Module Remote Air-Cooled 5 to 180 Tons 25

Specifications


Configuration & Size

Capacity:
5 to 180 tons
Models:
25 part numbers
Compressor:
Discus, Scroll
Tank & Pumps:
Separate pump-tank station
Refrigerant:
R-410A, R-454B

Construction

  • Compressors and evaporator on one frame
  • No reservoir or pumps on board
  • Remote condenser, galvanized cabinet
  • Copper tube, aluminum fin condenser coil
  • Multizone MZC controller

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • 0.80 / 0.60 / 0.40 at 40 / 30 / 20°F
  • Power: 230/3/60, 460/3/60, 575/3/60

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

MA Series Air-Cooled Chilling Modules

The Refrigeration Section, Without the Tank

An MA module is a chiller with no tank and no pumps. It carries the compressors, evaporator and controls, and connects to a separate pump-tank station that holds the fluid and runs the process and evaporator pumps. Twenty-five models run from 5 to 180 tons.

The suffix counts refrigeration zones: -C is one zone, -CC two, -CCC three. Two- and three-zone modules keep part of the capacity running when one circuit is down, and stage more finely on a partial load.

Condensers are remote and air-cooled, each module listed with its matched outdoor condenser, line connections and weight, and with the same 0.80 / 0.60 / 0.40 capacity multipliers at 40, 30 and 20°F as the TTI.

Modules are how a central plant grows. Adding an MA to an existing pump-tank station adds capacity without replacing the tank, the pumps or the header.



clear plastic bottles on a packaging conveyor line

Compressors and evaporator only; the pump-tank station and the condenser are separate.

Request a Quote

MA Series Chilling Modules Applications

Existing pump-tank stations
Existing pump-tank stations
Central plant expansion
Central plant expansion
Multi-zone redundancy
Multi-zone redundancy
Large molding plants
Large molding plants

schematic of the MA Series chilling modules with remote air-cooled condensers circuit, showing where the process fluid and the condenser heat go

What the Module Depends On

Because the MA carries no pumps, its performance is set by the station it is connected to. The evaporator flow has to match the module: too little and the evaporator runs cold and trips on freeze protection, too much and the pressure drop eats the evaporator pump's head. On a replacement, the station pump data matters as much as the module nameplate.

The nominal number needs the same caution as the TTI. The MA-100-RC-CC is listed at 90 tons and the MA-150-RC-CCC at 135, while the MA-7.5-RC-C is listed at 9.1. Size from the rated figure or the measured load. For the 35-ton single-zone, 70-ton two-zone and 105-ton three-zone sizes the alternate unit listed is the next module up; two smaller modules are the other option.

See pump tank stations and reservoirs.
Call and talk it through with an engineer: 1-805-484-2992

MA Chilling Modules: What to Know Before Sizing

Finer staging and a smaller loss when a zone drops: a three-zone module keeps about two-thirds of its output with one zone down, where a two-zone module keeps about half. The MA-180-RC-CCC carries six compressors on three zones, against four 30 HP scrolls, two to a zone, on the MA-120-RC-CC, and the MZC controller stages them as the load moves. A single-zone module such as the MA-25-RC-C, one 25 HP scroll, has no fallback at all. Decide first which load the plant cannot shed, then pick the zone count so the remaining zones carry it at the real setpoint.

About 6.9 and 54 tons. Both start from the listed figure, not the model number: the MA-10-RC-C is listed at 11.5 tons and the MA-100-RC-CC at 90, and Temptek's 0.60 multiplier at 30°F gives 6.9 and 54. Working from the names would give 6 and 60, under-crediting the small module and over-crediting the large one by 6 tons. Read the rated figure off the part-number page before applying any multiplier.

Roughly 60 GPM at a 10°F evaporator rise, on the water formula: 25 tons is 300,000 Btu/h, and 300,000 divided by 500 x 10 is 60. At a 30°F setpoint the module makes about 15 tons on the 0.60 multiplier, but the evaporator still needs steady flow, so do not throttle it down with the load. Glycol at the strength a 30°F loop needs needs somewhat more GPM than water would at an equal rise. The design evaporator flow for each module is part of the selection, so confirm it with us against the station pump curve before the module is ordered.

A place for its remote air-cooled condenser, the refrigerant line route to it and the condenser's power. Every MA comes paired with a named outdoor condenser in a galvanized cabinet with a copper tube, aluminum fin coil, and the part-number page gives its connections and weight, so the pad or roof steel can be checked before delivery. Line length and lift between module and condenser set line sizes, oil return and charge, and modules on R-454B follow that refrigerant's A2L installation rules. In a growing plant, leave room on the pad or roof for the condensers of modules still to come.

Four. Each makes about 48 tons at 20°F, 0.40 of it's 120-ton rating, so three give 144 tons, just short, and four give 192. Buying two because 240 nominal tons looks like plenty is the common error, and it leaves the plant near 96 tons on a cold-glycol duty. The fourth module also gives the bank spare zones when one is down for service. Before settling on four identical units, check whether a mix of sizes fits the load more closely; the station has to supply each module's evaporator flow either way. As the plant grows, each MA-120-RC-CC added later brings about 48 tons at 20°F, 72 at 30°F or 96 at 40°F, so the loop setpoint decides how far every addition goes, and a later move to colder glycol quietly shrinks the whole bank.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales