Refrigeration only: 5 to 180 tons of cooling for a plant that already has its tank, pumps and headers.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Chilling Module | Remote Air-Cooled | 5 to 180 Tons | 25 |
Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.
An MA module is a chiller with no tank and no pumps. It carries the compressors, evaporator and controls, and connects to a separate pump-tank station that holds the fluid and runs the process and evaporator pumps. Twenty-five models run from 5 to 180 tons.
The suffix counts refrigeration zones: -C is one zone, -CC two, -CCC three. Two- and three-zone modules keep part of the capacity running when one circuit is down, and stage more finely on a partial load.
Condensers are remote and air-cooled, each module listed with its matched outdoor condenser, line connections and weight, and with the same 0.80 / 0.60 / 0.40 capacity multipliers at 40, 30 and 20°F as the TTI.
Modules are how a central plant grows. Adding an MA to an existing pump-tank station adds capacity without replacing the tank, the pumps or the header.
Compressors and evaporator only; the pump-tank station and the condenser are separate.
Request a Quote
Because the MA carries no pumps, its performance is set by the station it is connected to. The evaporator flow has to match the module: too little and the evaporator runs cold and trips on freeze protection, too much and the pressure drop eats the evaporator pump's head. On a replacement, the station pump data matters as much as the module nameplate.
The nominal number needs the same caution as the TTI. The MA-100-RC-CC is listed at 90 tons and the MA-150-RC-CCC at 135, while the MA-7.5-RC-C is listed at 9.1. Size from the rated figure or the measured load. For the 35-ton single-zone, 70-ton two-zone and 105-ton three-zone sizes the alternate unit listed is the next module up; two smaller modules are the other option.
See pump tank stations and reservoirs.
Call and talk it through with an engineer: 1-805-484-2992