1-805-484-2992

Quotes - Sizing - Sales

MW-120-CC

Temptek
Product Type Capacity Refrigerant
Chilling Module Water-Cooled 120 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MW-120-CC as shown on this page.

Chiller equivalent to Temptek MW-120-CC

Description

The Temptek MW-120-CC is a water-cooled chilling module rated 120 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 4 scroll compressors of 30 HP each on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 96 tons at 40°F, 72 at 30°F and 48 at 20°F. Also available: the alternate CC-120WPT, the same water-cooled chilling module format and capacity class.

Product Overview

Part Number:
MW-120-CC
Manufacturer:
Temptek
Alternate Unit:
CC-120WPT

Configuration & Specifications

Refrigeration Zones Quantity:
2
Compressor Quantity:
4
Compressor HP:
30
Compressor Type:
Scroll
Total Capacity:
120
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing

Electrical

Voltage:
230V / 460V / 575V
Phase:
Three Phase
Frequency:
60 Hz
Full Load Amps:
528.0 (230V) / 264.0 (460V) / 212.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
4"
From Process Connection:
4"
Height:
70"
Width:
90"
Depth:
115"
Shipping Weight:
3,700 lbs

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales