Alternate unit for the Temptek MW Series Chilling Modules

MW Series Chilling Modules

Water-cooled refrigeration modules for a central plant with its own pump-tank station and tower water.

PRODUCT TYPE CAPACITY MODELS
Chilling Module Water-Cooled 5 to 180 Tons 25

Specifications


Configuration & Size

Capacity:
5 to 180 tons
Models:
25 part numbers
Compressor:
Discus, Scroll
Tank & Pumps:
Separate pump-tank station
Refrigerant:
R-407C, R-454B

Construction

  • Compressors and evaporator on one frame
  • No reservoir or pumps on board
  • Water-cooled condenser on board
  • UL-listed electrical components
  • Multizone MZC controller

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • 0.80 / 0.60 / 0.40 at 40 / 30 / 20°F
  • Power: 230/3/60, 460/3/60, 575/3/60

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

MW Series Water-Cooled Chilling Modules

Module Capacity, Tower-Water Condensing

The MW is the water-cooled twin of the MA module: compressors, evaporator and a water-cooled condenser on a frame, no tank and no pumps. Twenty-five models run from 5 to 180 tons in one, two and three refrigeration zones (-C, -CC, -CCC).

With the condenser on board, nothing is field-piped with refrigerant. The module needs chilled-fluid connections to the pump-tank station and condenser water from a tower or plant loop.

Ratings and multipliers follow the rest of the central range: rated at 50°F leaving water, with 0.80, 0.60 and 0.40 multipliers at 40, 30 and 20°F.

Condenser water is published for three sizes only - the MW-35-C, MW-70-CC and MW-105-CCC, at 33.5 to 157.5 GPM of city water or 105 to 315 GPM of tower water. For the other sizes we work it out from the load and the tower conditions.



paper mill production line with large paper rolls

Compressors, evaporator and water-cooled condenser on a frame; tank and pumps are separate.

Request a Quote

MW Series Chilling Modules Applications

Tower-water plants
Tower-water plants
Existing pump-tank stations
Existing pump-tank stations
Multi-zone redundancy
Multi-zone redundancy
Extrusion and packaging
Extrusion and packaging

schematic of the MW Series water-cooled chilling modules circuit, showing where the process fluid and the condenser heat go

Three Systems Meet at One Module

An MW module sits at the junction of three systems: the refrigeration circuit it carries, the chilled fluid from the pump-tank station and the condenser water from the tower. A replacement has to satisfy all three. The evaporator flow has to suit the station, the condenser flow has to suit the tower, and the capacity has to suit the load at the real setpoint.

The published MW data is thinner than the MA data. Several sizes list capacity and electrical figures only, and a few repeat the MA figures exactly, so on an MW replacement the nameplate and a measured load are worth more than usual. For the 35, 70 and 105-ton sizes the alternate unit listed is the next size up.

See condenser water planning.
Call and talk it through with an engineer: 1-805-484-2992

Operating Questions: MW Water-Cooled Modules

From the load and the tower supply temperature, and the flow is confirmed on request rather than scaled from another size. The three published sizes, 105 GPM on the MW-35-C, 210 on the MW-70-CC and 315 on the MW-105-CCC, come to about 3 GPM of tower water per nominal ton, which is a useful cross-check but not a rating for a module that has none. Warmer tower water needs more flow for the same heat. Do not scale from the city-water figures, which do not follow one ratio across the three sizes. Send the tower supply temperature on a design day with the module choice.

Three: chilled-fluid piping to the pump-tank station through 6-inch connections, tower or plant-loop water for the condenser, and a three-phase feed at 230, 460 or 575 V. The condenser branch on a module this size is large, so check the tower header well before delivery. The smallest module, the MW-10-C, connects at 1-1/4 inches. With the condenser on the frame, the refrigeration circuit arrives complete and the contractor does no refrigerant work on site.

When the plant already runs a cooling tower with capacity to spare and has nowhere good for outdoor condensers. The MW keeps its condenser on the frame, so there is no roof steel, no condenser pad and no refrigerant line run, but it adds a tower load of about 3 GPM per ton on the published sizes, 315 GPM for an MW-105-CCC. The MA rejects its heat to outdoor air instead and needs no tower at all. Where the tower is old, fouled or already at its limit, the MA is usualy the simpler choice even with the line work. We can price both side by side.

About 96 tons at 40°F and 48 at 20°F, from its 120-ton rating at 50°F and Temptek's 0.80 and 0.40 multipliers; at 30°F it is about 72. The four 30 HP scrolls sit on two zones, so with one zone out the module keeps roughly half: around 48 tons at 40°F or 24 at 20°F. Because a few MW pages repeat the MA figures exactly, the MW-120-CC rating is confirmed on request before a selection rests on these numbers.