Water-cooled refrigeration modules for a central plant with its own pump-tank station and tower water.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Chilling Module | Water-Cooled | 5 to 180 Tons | 25 |
Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.
The MW is the water-cooled twin of the MA module: compressors, evaporator and a water-cooled condenser on a frame, no tank and no pumps. Twenty-five models run from 5 to 180 tons in one, two and three refrigeration zones (-C, -CC, -CCC).
With the condenser on board, nothing is field-piped with refrigerant. The module needs chilled-fluid connections to the pump-tank station and condenser water from a tower or plant loop.
Ratings and multipliers follow the rest of the central range: rated at 50°F leaving water, with 0.80, 0.60 and 0.40 multipliers at 40, 30 and 20°F.
Condenser water is published for three sizes only - the MW-35-C, MW-70-CC and MW-105-CCC, at 33.5 to 157.5 GPM of city water or 105 to 315 GPM of tower water. For the other sizes we work it out from the load and the tower conditions.
Compressors, evaporator and water-cooled condenser on a frame; tank and pumps are separate.
Request a Quote
An MW module sits at the junction of three systems: the refrigeration circuit it carries, the chilled fluid from the pump-tank station and the condenser water from the tower. A replacement has to satisfy all three. The evaporator flow has to suit the station, the condenser flow has to suit the tower, and the capacity has to suit the load at the real setpoint.
The published MW data is thinner than the MA data. Several sizes list capacity and electrical figures only, and a few repeat the MA figures exactly, so on an MW replacement the nameplate and a measured load are worth more than usual. For the 35, 70 and 105-ton sizes the alternate unit listed is the next size up.
See condenser water planning.