1-805-484-2992

Quotes - Sizing - Sales

MW-20-CC

Temptek
Product Type Capacity Refrigerant
Chilling Module Water-Cooled 23 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MW-20-CC as shown on this page.

Chiller equivalent to Temptek MW-20-CC

Description

The Temptek MW-20-CC is a water-cooled chilling module rated 23 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 2 scroll compressors of 10 HP each on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 18.4 tons at 40°F, 13.8 at 30°F and 9.2 at 20°F. Also available: the alternate CC-20WPT, the same water-cooled chilling module format and capacity class.

Product Overview

Part Number:
MW-20-CC
Manufacturer:
Temptek
Alternate Unit:
CC-20WPT

Configuration & Specifications

Refrigeration Zones Quantity:
2
Compressor Quantity:
2
Compressor HP:
10
Compressor Type:
Scroll
Total Capacity:
23
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing

Electrical

Voltage:
230V / 460V / 575V
Phase:
Three Phase
Frequency:
60 Hz
Full Load Amps:
88.0 (230V) / 44.0 (460V) / 36.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
2"
From Process Connection:
2"
Height:
57"
Width:
48"
Depth:
76"
Shipping Weight:
1,200 lbs

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales