| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Chilling Module | Water-Cooled | 90 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n MW-90-CCC as shown on this page.
The Temptek MW-90-CCC is a water-cooled chilling module rated 90 tons at 50°F leaving fluid and 115°F condensing temperature, on 3 refrigeration zones. It runs 3 scroll compressors of 30 HP each on R-454B. As a chilling module it carries no reservoir or pumps; it connects to a separate pump-tank station. At a glycol setpoint the published multipliers apply: about 72 tons at 40°F, 54 at 30°F and 36 at 20°F. Also available: the alternate CCC-90WPT, the same water-cooled chilling module format and capacity class.