Description
The Temptek TTI-100A is a central chiller with remote air-cooled condensers rated 90 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 4 scroll compressors of 25 HP each on R-454B. The process pump delivers 300 GPM at 60 PSI (15 HP) from a 1,200 gallons reservoir. It is paired with the KCL-157-KR remote air-cooled condenser (8 fans). At a glycol setpoint the published multipliers apply: about 72 tons at 40°F, 54 at 30°F and 36 at 20°F. Also available: the alternate TI-100A, the same air-cooled central format and capacity class.
Product Overview
Part Number:
TTI-100A
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
2
Compressor Quantity:
4
Compressor Horsepower:
25
Compressor Type:
Scroll
Total Capacity:
90 tons
Refrigerant Type:
R-454B
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 15
- Process Pump GPM: 300
- Process Pump PSI: 60
- Evaporator Pump HP: 5
- Evaporator Pump GPM: 225
- Reservoir Operating: 1,200 gallons
- Reservoir Holding: 1,475 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 456.0 (230V) / 228.0 (460V) / 183.0 (575V)
Remote Condenser
Circuits Served:
2
Fans:
8
Fan RPM:
1,140
Hot Gas Connection:
2-5/8"
Liquid Connection:
2-1/8"
Fan Motor Voltage:
460V
Fan Motor Phase:
Single Phase
Fan Motor Frequency:
60 Hz
Fan Motor Full Load Amps:
23.2
Tube Material:
Copper
Fin Material:
Aluminum
Coil Coating:
None
Fins Per Inch:
12
Height:
54"
Width:
86-5/8"
Depth:
222-1/2"
Shipping Weight:
3,025 lbs
Condenser Model:
KCL-157-KR
Connections, Dimensions & Weight
To Process Connection:
4"
From Process Connection:
4"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
4"
Height:
112"
Width:
136"
Depth:
128"
Shipping Weight:
6,505 lbs
Operating Weight:
17,705 lbs