One chiller plant for a whole molding floor: 20 to 180 tons, a baffled tank, two pumps and condensers outdoors.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Central Chiller | Remote Air-Cooled | 20 to 180 Tons | 12 |
Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.
The TTI is a complete central chiller: two to six scroll compressors on two or three refrigeration zones, a baffled tank of 340 operating gallons (1,200 on the largest sizes), a process pump and a separate evaporator pump. Twelve models run from 20.5 to 180 tons.
Two pumps, two jobs. The evaporator pump circulates the cold side of the tank through the evaporator; the process pump sends chilled fluid out to the header. That split keeps evaporator flow constant however many machines are open on the header.
The air-cooled versions use remote condensers. Each size is listed with its matched outdoor condenser - the KCL model, fan count, line connections and weight - so the heat of the whole plant leaves the building.
Ratings are at 50°F, with published multipliers below it: 0.80 at 40°F, 0.60 at 30°F and 0.40 at 20°F. A TTI-80A at a 30°F glycol setpoint is a 48-ton chiller.
The zone count is the first thing to preserve on a replacement. A TTI-60A has two refrigeration zones; lose a compressor and the plant carries on at roughly half capacity while it is repaired. Replace it with a single large compressor and that fallback disappears.
The second is the rated capacity, which is not always the number in the name. The TTI-100A is listed at 90 tons and the TTI-150A at 135. If the plant has been running happily on a TTI-100A, the load is at most 90 tons, and a new 100-ton unit is already a step up. If it has been struggling, the load has grown past 90 and sizing should start from the header, not the old nameplate.
Then check the pumps: process flow runs from 48 GPM on the 20-ton unit to 540 on the 180, at 55 to 70 PSI. Headers that have grown since installation often need more pressure than the original pump had. See the tonnage and capacity guide.
Call and talk it through with an engineer: 1-805-484-2992