Alternate unit for the Temptek TTI Series Air-Cooled

TTI Series Air-Cooled

One chiller plant for a whole molding floor: 20 to 180 tons, a baffled tank, two pumps and condensers outdoors.

PRODUCT TYPE CAPACITY MODELS
Central Chiller Remote Air-Cooled 20 to 180 Tons 12

Specifications


Configuration & Size

Capacity:
20.5 to 180 tons
Models:
12 part numbers
Compressor:
Scroll
Process Flow:
48 to 540 GPM
Refrigerant:
R-454B

Construction

  • Rotationally molded polyethylene tank
  • Hot / cold baffled reservoir
  • Separate process and evaporator pumps
  • Brazed-plate evaporators, stainless plates
  • Remote condensers, copper tube / aluminum fin

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • 0.80 / 0.60 / 0.40 at 40 / 30 / 20°F
  • Power: 230/3/60, 460/3/60, 575/3/60

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

TTI Series Air-Cooled Central Chillers

A Central Plant on One Skid

The TTI is a complete central chiller: two to six scroll compressors on two or three refrigeration zones, a baffled tank of 340 operating gallons (1,200 on the largest sizes), a process pump and a separate evaporator pump. Twelve models run from 20.5 to 180 tons.

Two pumps, two jobs. The evaporator pump circulates the cold side of the tank through the evaporator; the process pump sends chilled fluid out to the header. That split keeps evaporator flow constant however many machines are open on the header.

The air-cooled versions use remote condensers. Each size is listed with its matched outdoor condenser - the KCL model, fan count, line connections and weight - so the heat of the whole plant leaves the building.

Ratings are at 50°F, with published multipliers below it: 0.80 at 40°F, 0.60 at 30°F and 0.40 at 20°F. A TTI-80A at a 30°F glycol setpoint is a 48-ton chiller.



plastics extrusion line with long barrels in a factory

Tank, evaporator pump and process pump on the skid; multiple zones share the load.

Request a Quote

TTI Series Air-Cooled Applications

Multi-press molding floors
Multi-press molding floors
Die casting cells
Die casting cells
Plant chilled-water headers
Plant chilled-water headers
Redundant zone operation
Redundant zone operation

schematic of the TTI Series air-cooled central chillers circuit, showing where the process fluid and the condenser heat go

Zones, Headers and the Nominal Number

The zone count is the first thing to preserve on a replacement. A TTI-60A has two refrigeration zones; lose a compressor and the plant carries on at roughly half capacity while it is repaired. Replace it with a single large compressor and that fallback disappears.

The second is the rated capacity, which is not always the number in the name. The TTI-100A is listed at 90 tons and the TTI-150A at 135. If the plant has been running happily on a TTI-100A, the load is at most 90 tons, and a new 100-ton unit is already a step up. If it has been struggling, the load has grown past 90 and sizing should start from the header, not the old nameplate.

Then check the pumps: process flow runs from 48 GPM on the 20-ton unit to 540 on the 180, at 55 to 70 PSI. Headers that have grown since installation often need more pressure than the original pump had. See the tonnage and capacity guide.
Call and talk it through with an engineer: 1-805-484-2992

TTI Air-Cooled Central Chillers in Practice

So the cold side of the tank is always overfed. The 3 HP evaporator pump moves 160 GPM through the evaporator while the 7.5 HP process pump sends 120 GPM at 60 PSI to the header, and the surplus returns across the baffle instead of warm return being drawn into the supply. That keeps the process supply at setpoint even with every machine on the header open. The process pump carries more horsepower because it works against the header's pressure drop. If process flow is ever raised above evaporator flow, warm return mixes into the supply and the header runs warm.

About 2 tons: the TTI-90A is listed at 85.5 tons at 50°F, so Temptek's 0.40 multiplier at 20°F gives 34.2 tons, while 90 nominal tons would suggest 36. That 1.8-ton gap matters when the load is close to the unit. A plant moving a TTI from a 40°F loop to a 20°F one halves its capacity, from 0.80 of the rating to 0.40, so the setpoint change alone can turn a comfortable selection into a short one. Size from the listed rating at your setpoint.

About two-thirds, roughly 90 of its 135 listed tons at 50°F, because its six 25 HP scrolls sit on three zones. At a 30°F setpoint that is about 54 tons out of 81. The TTI-60A, with two 30 HP scrolls on two zones, drops to about half, and the TTI-90A's three compressors on three zones leave two-thirds. If the plant must hold a minimum load through a compressor repair, check it against the remaining zones at the real setpoint, not against the nameplate. A molding floor that needs 50 tons of 30°F glycol to keep its critical presses running is covered by the TTI-150A on two zones, about 54 tons, but not by a TTI-90A, which at 30°F makes about 51 tons with all three zones and about 34 with two.

Usually, yes: the TTI-100A weighs 17,705 lbs in operation with its 1,200-gallon tank full, close to 9 tons on one skid. The fluid alone is roughly 10,000 lbs, so the operating weight, not the shipping weight, is the figure for the slab. The TTI-150A reaches 23,820 lbs, while the TTI-50A, with 340 operating gallons, is 9,650. Outdoors, the matched KCL condenser adds its own load: 3,025 lbs for the eight-fan unit paired with the TTI-100A, which on a roof means checking the steel as well. Plan rigging and the route to the set location before the delivery date.