Description

The Temptek TTI-120WD is a water-cooled central chiller rated 120 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 4 scroll compressors of 30 HP each on R-454B. The process pump delivers 360 GPM at 65 PSI (20 HP) from a 1,200 gallons reservoir. Condenser water is listed at 173 GPM of 60°F city water or 346 GPM of 85°F tower water. Also available: the alternate TI-120WD, the same water-cooled central format and capacity class.

Product Overview

Part Number:
TTI-120WD
Manufacturer:
Temptek
Alternate Unit:
TI-120WD

Configuration & Specifications

Refrigeration Zones Quantity:
2
Compressor Quantity:
4
Compressor Horsepower:
30
Compressor Type:
Scroll
Total Capacity:
120 tons
Refrigerant Type:
R-454B
Condenser City Water:
173 GPM
Condenser Tower Water:
346 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing

Process Pump & Reservoir

  • Process Pump HP: 20
  • Process Pump GPM: 360
  • Process Pump PSI: 65
  • Evaporator Pump HP: 5
  • Evaporator Pump GPM: 277
  • Reservoir Operating: 1,200 gallons
  • Reservoir Holding: 1,475 gallons

Electrical

  • Voltage: 230V / 460V / 575V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Full Load Amps: 588.0 (230V) / 294.0 (460V) / 236.0 (575V)

Connections, Dimensions & Weight

To Process Connection:
4"
From Process Connection:
4"
Water Make-Up Connection:
1-1/2"
Overflow Connection:
4"
Condenser Connection:
4"
Height:
114"
Width:
147"
Depth:
147"
Shipping Weight:
6,705 lbs
Operating Weight:
17,905 lbs