The water-cooled central plant: 20 to 180 tons on one skid, condensing to tower water instead of outdoor air.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Central Chiller | Water-Cooled | 20 to 180 Tons | 14 |
Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.
Fourteen models run from 20.5 to 180 tons with the same skid as the air-cooled TTI - baffled tank, evaporator pump, process pump, two or three refrigeration zones - and shell-and-tube water-cooled condensers on board, so nothing is field-piped with refrigerant.
The WD models are a separate build at 120, 150 and 180 tons, listed beside the W versions with their own capacities: the TTI-150WD at 147 tons against 150 for the TTI-150W.
Condenser water is published both ways: city water at 60°F and tower water at 85°F, for a clean condenser. The TTI-150W needs 224 GPM of city water or 448 GPM from a tower.
Ratings are at 50°F leaving water and 105°F condensing, with the same multipliers below 50°F as the air-cooled range.
A packaged central chiller that condenses to a cooling tower, with tank and pumps on the skid.
Request a Quote
A water-cooled central chiller sits between two water systems, and a replacement has to be checked against both. On the process side: header flow, pressure and setpoint, exactly as for the air-cooled unit. On the condenser side: tower flow, supply temperature and the tower's remaining capacity. A tower that has been fouling for ten years may no longer deliver 85°F water on a design day, and the new chiller will be blamed for the high-pressure trips.
Tower flow runs at roughly three gallons per minute per ton accross this range - 61 GPM on the TTI-20W, 534 GPM on the largest units - and the condenser connections are listed on each part-number page. If the tower pump and piping were sized for a smaller chiller than the one going in, they are the bottleneck.
See condenser water planning.