| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Central Chiller | Water-Cooled | 20.5 Tons | R-454B |
Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n TTI-20W as shown on this page.
The Temptek TTI-20W is a water-cooled central chiller rated 20.5 tons at 50°F leaving fluid and 105°F condensing temperature, on 2 refrigeration zones. It runs 2 scroll compressors of 10 HP each on R-454B. The process pump delivers 48 GPM at 60 PSI (5 HP) from a 340 gallons reservoir. Condenser water is listed at 31 GPM of 60°F city water or 61 GPM of 85°F tower water. At a glycol setpoint the published multipliers apply: about 16.4 tons at 40°F, 12.3 at 30°F and 8.2 at 20°F. Also available: the alternate TI-20W, the same water-cooled central format and capacity class.