Description
The Temptek TTI-40W is a water-cooled central chiller rated 40 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs 2 scroll compressors of 20 HP each on R-454B. The process pump delivers 96 GPM at 60 PSI (7.5 HP) from a 340 gallons reservoir. Condenser water is listed at 60 GPM of 60°F city water or 120 GPM of 85°F tower water. Also available: the alternate TI-40W, the same water-cooled central format and capacity class.
Product Overview
Part Number:
TTI-40W
Manufacturer:
Temptek
Configuration & Specifications
Refrigeration Zones Quantity:
2
Compressor Quantity:
2
Compressor Horsepower:
20
Compressor Type:
Scroll
Total Capacity:
40 tons
Refrigerant Type:
R-454B
Condenser City Water:
60 GPM
Condenser Tower Water:
120 GPM
Rating Basis:
50°F leaving fluid, 115°F condensing
Process Pump & Reservoir
- Process Pump HP: 7.5
- Process Pump GPM: 96
- Process Pump PSI: 60
- Evaporator Pump HP: 3
- Evaporator Pump GPM: 96
- Reservoir Operating: 340 gallons
- Reservoir Holding: 400 gallons
Electrical
- Voltage: 230V / 460V / 575V
- Phase: Three Phase
- Frequency: 60 Hz
- Full Load Amps: 190.0 (230V) / 95.0 (460V) / 76.0 (575V)
Connections, Dimensions & Weight
To Process Connection:
3"
From Process Connection:
3"
Water Make-Up Connection:
1"
Overflow Connection:
4"
Condenser Connection:
3"
Height:
82"
Width:
92"
Depth:
96"
Shipping Weight:
4,350 lbs
Operating Weight:
8,710 lbs