1-805-484-2992

Quotes - Sizing - Sales

TTOACS-210D-MZC-2P

Temptek
Product Type Capacity Refrigerant
Outdoor Chiller Outdoor 188 Tons R-513A

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n TTOACS-210D-MZC-2P as shown on this page.

Chiller equivalent to Temptek TTOACS-210D-MZC-2P

Description

The Temptek TTOACS-210D-MZC-2P is a outdoor air-cooled central chiller rated 188 tons at 50°F leaving fluid and 115°F condensing temperature, on 2 refrigeration zones. It runs a rotary screw compressor on R-513A. The process pump delivers 490 GPM at 60 PSI (30 HP) from a 900 gal reservoir. At a glycol setpoint the published multipliers apply: about 150.4 tons at 40°F, 112.8 at 30°F and 75.2 at 20°F. Also available: alternate outdoor air-cooled central chillers to 210 tons, selected from the load for this size.

Product Overview

Part Number:
TTOACS-210D-MZC-2P
Also Printed As:
TTOACS-200D-MZC-2P
Manufacturer:
Temptek
Series:
TTOACS Series

Configuration & Specifications

Refrigeration Zones Quantity:
2
Capacity (Tons):
188
Capacity (kW):
661
Compressor Type:
Rotary Screw
Refrigerant Type:
R-513A
Condenser Quantity of Fans:
14
Evaporator Type:
Shell and Tube
Controller Type:
MZC Series
Rating Basis:
50°F leaving fluid, 115°F condensing

Connections, Dimensions & Weight

Connection Type:
Flanged
Connection Size:
6"
Height:
99"
Width:
96"
Depth:
408"

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales