1-805-484-2992

Quotes - Sizing - Sales

TTOACS-60S-CG-1P

Temptek
Product Type Capacity Refrigerant
Outdoor Chiller Outdoor 55.1 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n TTOACS-60S-CG-1P as shown on this page.

Chiller equivalent to Temptek TTOACS-60S-CG-1P

Description

The Temptek TTOACS-60S-CG-1P is a outdoor air-cooled central chiller rated 55.1 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a tandem scroll compressor on R-454B. The process pump delivers 144 GPM at 60 PSI (7.5 HP) from a 300 gal reservoir. At a glycol setpoint the published multipliers apply: about 44.08 tons at 40°F, 33.06 at 30°F and 22.04 at 20°F. Also available: the alternate OACS-60S-MG-2P, the same outdoor air-cooled format and capacity class.

Product Overview

Part Number:
TTOACS-60S-CG-1P
Also Printed As:
TTOACS-60S-CG-2P
Manufacturer:
Temptek
Series:
TTOACS Series
Alternate Unit:
OACS-60S-MG-2P

Configuration & Specifications

Refrigeration Zones Quantity:
1
Capacity (Tons):
55.1
Capacity (kW):
193.3
Compressor Type:
Tandem Scroll
Refrigerant Type:
R-454B
Condenser Quantity of Fans:
6
Evaporator Type:
Brazed Plate
Controller Type:
MG Series
Rating Basis:
50°F leaving fluid, 115°F condensing

Process Pump & Reservoir

  • Process Pump HP: 7.5
  • Process Pump GPM: 144
  • Process Pump PSI: 60
  • Evaporator Pump HP: 5
  • Evaporator Pump GPM: 175
  • Standby Pump Offered: Optional
  • Reservoir: 300 gal
  • Reservoir Construction: Polyethylene

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • System Amps: 168.0

Connections, Dimensions & Weight

Connection Type:
Flanged
Connection Size:
3"
Height:
104"
Width:
97"
Depth:
180"