1-805-484-2992

Quotes - Sizing - Sales

EQ4A03

Thermal Care
Product Type Capacity Refrigerant
Portable Chiller Air-Cooled Portable 3 Tons @ 50°F R-454B

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n EQ4A03 as shown on this page.

Replacement chiller for the Thermal Care EQ4A03

Description

The Thermal Care EQ4A03 is an air-cooled portable chiller from the Accuchiller EQ Series. Thermal Care publishes it at 3 tons (11 kW) at 50°F leaving coolant, 95°F ambient air, with a 20 to 65°F set point range. It runs one scroll compressor, on R-454B. It carries an 11-gallon reservoir and a 1 hp process pump rated 7 GPM at 38 PSI. Replacement: we supply the Temptek CG-4A, an air-cooled portable chiller rated 4 tons at 50°F, against the 3 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
EQ4A03
Manufacturer:
Thermal Care
Replacement Unit:
Temptek CG-4A

Published Capacity

Cooling Capacity:
3 tons (11 kW)
Rating Basis:
50°F leaving coolant, 95°F ambient air
Set Point Range:
20 to 65°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-454B
Condenser:
Air-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, Modbus RTU

Pump & Reservoir

  • Reservoir: 11 gallons
  • Process Pump: 1 hp
  • Pump Flow: 7 GPM
  • Pump Pressure: 38 PSI

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 11 A
  • Maximum Overcurrent Protection: 20 A
  • MCA, Other Voltages (series table): 23 A (230V three-phase) / 9 A (575V three-phase)

Dimensions & Weight

Dimensions (L x W x H):
40 x 24 x 44 in
Shipping Weight:
430 lbs (195 kg)
Operating Weight:
520 lbs (236 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales