Replacement unit for the Thermal Care EQ Series

EQ Series

The smallest Accuchillers: 1 to 3 tons in a compact cabinet, air-cooled, water-cooled or with a remote condenser, for one machine or one instrument.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Portable 1 to 3 Tons 6

Specifications


Configuration & Size

Capacity:
1 to 3 Tons at 50°F
Models:
6 part numbers
Compressor:
One scroll
Process Flow:
2 to 8 GPM
Refrigerant:
R-454B

Construction

  • One scroll compressor
  • Stainless brazed plate evaporator
  • Polyethylene reservoir, 3 or 11 gallons
  • Stainless process pump
  • Process Y-strainer, hot gas bypass

Ratings

  • Rated at 50°F leaving coolant
  • 95°F ambient or 85°F water
  • Refrigerant R-454B
  • Set point 20 to 65°F

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

EQ Series Portable Chillers, 1 to 3 Tons

One Machine, One Chiller

Six models in three condenser styles. The EQ4A01, EQ4A02 and EQ4A03 are air-cooled, the EQ4W02 and EQ4W03 water-cooled, and the EQ4R03 a 3-ton unit with a remote air-cooled condenser. Each runs one scroll compressor into a stainless steel brazed plate evaporator, with a polyethylene reservoir and a stainless process pump on board.

Capacity is published at 50°F leaving coolant, in a 95°F ambient for the air-cooled units and on 85°F condenser water for the water-cooled ones, on R-454B. The set point range is 20 to 65°F, narrower at the warm end than the NQ line.

The 1-ton is a different cabinet. The EQ4A01 is 28 x 19 x 30 inches with a 3-gallon reservoir and a 1/4 hp pump rated 2 GPM at 80 PSI, on 230 V single-phase. The 2 and 3-ton units share a 40 x 24 inch footprint, an 11-gallon reservoir and a 1 hp pump delivering 5 to 8 GPM at 38 to 39 PSI.

Voltage choices widen above 1 ton. Thermal Care's series table lists the 2 and 3-ton units on 230, 460 and 575 V three-phase; the unit pages give the 460 V figures.



rows of blue molded plastic containers

Scroll compressor, brazed plate evaporator, reservoir and pump in a cabinet small enough to sit beside the machine.

Request a Quote

EQ Series Applications

Laser and optics cooling
Laser and optics cooling
Machine spindles
Machine spindles
Lab and analytical instruments
Lab and analytical instruments
Small molding presses
Small molding presses

schematic of the EQ series circuit, showing where the process fluid and the condenser heat go

Sized to the Machine, Not the Plant

An EQ does one job: it holds a single load at temperature, right beside it. That keeps the hose runs short and the pressure drop low, which matters on a 1-ton unit whose pump delivers 2 GPM. The air-cooled models reject their heat into the room, about 1.25 times the cooling load, so a closed lab or a small enclosure has to be able to take it; the water-cooled models and the remote-condenser EQ4R03 move that heat elsewhere.

Check the flow before the tonnage. Many small loads, a laser or a spindle, are specified by flow and pressure at the inlet as much as by heat load, and the 1-ton's pump is a high-head, low-flow pump. The glycol chiller sizing guide works the heat load from flow and temperture rise.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the EQ's published 50°F capacity in the same condenser style. The 1-ton maps to a Temptek CF fractional-ton unit, and the 3-ton remote-condenser model to the smallest Temptek remote-condenser unit, rated 4.9 tons.
Call and talk it through with an engineer: 1-805-484-2992

Thermal Care EQ Portables: Cross-Reference Questions

On paper yes, 2 tons at 50°F leaving coolant, but each at its own rating condition: the EQ4A02 in a 95°F ambient and the EQ4W02 on 85°F condenser water. The two drift apart in service. The air-cooled unit loses capacity in a hot room, and the water-cooled unit loses it when building water runs warmer than 85°F, which tower water often does in summer. Tell us which one you have and where its heat goes, because the replacement keeps the same condenser style and is sized to the 50°F figure.

It should not: the EQ4A01 lists 11 A minimum circuit ampacity and a 20 A maximum overcurrent device on 230 V single-phase, which describes a circuit of its own. Shared, the breaker can trip when the compressor starts under other load. The MOP is the largest breaker allowed, not a margin to borrow. If the old unit's outlet also feeds instruments, plan a dedicated circuit for the CF-1A that replaces it.

About 45,000 BTU/hr at full load: 3 tons is 36,000 BTU/hr of process heat, and the condenser rejects roughly 1.25 times that once the compressor's work is added. The 2-ton EQ4A02 adds about 30,000 BTU/hr. The 1-ton EQ4A01 adds about 15,000 BTU/hr on the same basis. In a sealed lab sized for people and instruments, that can exceed what the room's cooling was designed to remove, and the symptom is a room that warms through the afternoon while the chiller's own capacity sags with it. The water-cooled EQ4W02 and EQ4W03, or the remote-condenser EQ4R03, carry that heat outside the room instead.

The Temptek CGD-5A-RC, rated 4.9 tons at 50°F, because it is the smallest remote-condenser unit in the Temptek line; that leaves about 1.9 tons over the EQ4R03's 3-ton rating. Both ratings are taken at 50°F leaving fluid, so the comparison needs no correction. The extra capacity is no risk to holding temperature, though on a light, steady load the unit will cycle more, and the remote condenser and refrigerant lines are checked for the new unit rather than assumed from the EQ's pair. Measure the line length and the rise to the condenser before the quote.