Replacement chiller for the Thermal Care KSEA040

Description

The Thermal Care KSEA040 is a packaged outdoor air-cooled chiller from the Accuchiller KSE Series. Thermal Care publishes it at 40 tons (141 kW) at 50°F leaving coolant, 95°F ambient air, with a 20 to 80°F set point range. It runs two scroll compressors, on two refrigeration circuits, on R-454B or R-410A. The pumps are an option: 7.5 hp standard-pressure for 96 GPM at 41 PSI, or 15 hp high-pressure at 86 PSI. Replacement: we supply the Temptek TTOACS-50D-MZC-2P, an outdoor air-cooled packaged chiller rated 48.4 tons at 50°F, against the 40 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like. It is a dual-zone unit, so the two-circuit redundancy carries over.

Product Overview

Part Number:
KSEA040
Manufacturer:
Thermal Care
Replacement Unit:
Temptek TTOACS-50D-MZC-2P

Published Capacity

Cooling Capacity:
40 tons (141 kW)
Rating Basis:
50°F leaving coolant, 95°F ambient air
Set Point Range:
20 to 80°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
2
Refrigeration Circuits:
Two
Refrigerant:
R-454B or R-410A
Condenser:
Air-Cooled Microchannel
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, Color Touch Screen

Pump & Reservoir

  • Pump Package, Standard Pressure: 7.5 hp, 96 GPM at 41 PSI
  • Pump Package, High Pressure: 15 hp at 86 PSI
  • Integral Tank: Optional (KSE with Tank)

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 89 A
  • Maximum Overcurrent Protection: 125 A

Connections

Process Connections:
3 in
Process Connections, High Flow:
4 in

Dimensions & Weight

Dimensions (L x W x H):
128 x 47 x 79 in
Shipping Weight:
2,876 lbs (1,305 kg)
Operating Weight:
2,976 lbs (1,350 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.