1-805-484-2992

Quotes - Sizing - Sales

NQA04

Thermal Care
Product Type Capacity Refrigerant
Portable Chiller Air-Cooled Portable 4 Tons @ 50°F R-454B or R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n NQA04 as shown on this page.

Replacement chiller for the Thermal Care NQA04

Description

The Thermal Care NQA04 is an air-cooled portable chiller from the Accuchiller NQ Series. Thermal Care publishes it at 4 tons (14 kW) at 50°F leaving coolant, 95°F ambient air, with a 20 to 80°F set point range. It runs one scroll compressor, on R-454B or R-410A. It carries a 14-gallon reservoir and a 2 hp process pump rated 10 GPM at 43 PSI. Replacement: we supply the Temptek CG-4A, an air-cooled portable chiller rated 4 tons at 50°F, against the 4 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
NQA04
Manufacturer:
Thermal Care
Replacement Unit:
Temptek CG-4A

Published Capacity

Cooling Capacity:
4 tons (14 kW)
Rating Basis:
50°F leaving coolant, 95°F ambient air
Set Point Range:
20 to 80°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-454B or R-410A
Condenser:
Air-Cooled Microchannel
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, 7-inch Color Touch Screen
Sound Pressure:
74 dBA at 1 m

Pump & Reservoir

  • Reservoir: 14 gallons
  • Process Pump: 2 hp
  • Pump Flow: 10 GPM
  • Pump Pressure: 43 PSI

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 16 A
  • Maximum Overcurrent Protection: 25 A

Connections

Process Connections:
1-1/2 in

Dimensions & Weight

Dimensions (L x W x H):
48 x 34 x 61 in
Shipping Weight:
720 lbs (327 kg)
Operating Weight:
810 lbs (367 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales