Replacement unit for the Thermal Care NQ Series Air-Cooled

NQ Series Air-Cooled

Thermal Care's workhorse portable: 4 to 31 tons, air-cooled with microchannel condensers, scroll compressors and a PLC with a 7-inch touch screen.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Air-Cooled Portable 4 to 31 Tons 9

Specifications


Configuration & Size

Capacity:
4 to 31 Tons at 50°F
Models:
9 part numbers
Compressor:
One or two scroll
Process Flow:
10 to 72 GPM
Refrigerant:
R-454B, R-410A

Construction

  • Scroll compressors, one or two
  • Microchannel aluminum condenser
  • Stainless brazed plate evaporator
  • Electronic expansion valve
  • Stainless process pump, poly reservoir

Ratings

  • Rated at 50°F leaving coolant
  • 95°F ambient air
  • R-454B or R-410A
  • Power: 460/3/60 published

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

NQ Air-Cooled Portable Chillers, 4 to 31 Tons

The Portable Beside the Press

Nine models, one or two scroll compressors. The NQA04 to NQA15 run one compressor and the NQA20 to NQA30 two, each into a stainless steel brazed plate evaporator with an electronic expansion valve, on R-454B or R-410A. Condensers are all-aluminum microchannel coils with TEAO fan motors and a cleanable inlet filter.

Capacity is published at 50°F leaving coolant and 95°F ambient. The unit pages list 4 to 31 tons, usually a little above the model number: the NQA10 at 11 tons, the NQA25 at 26. The set point range is 20 to 80°F.

Tank and pump grow in steps. Reservoirs run 14 to 67 gallons and the stainless process pump 2 to 5 hp, delivering 10 GPM at 43 PSI on the NQA04 up to 72 GPM at 43 PSI on the NQA30. Process connections are 1-1/2 inch to the NQA13 and 2 inch above.

It is loud at the top. Thermal Care publishes sound pressure at 1 meter of 74 dBA on the smallest units rising to 86 dBA on the NQA30, and the 15-ton and larger cabinets stand 94 inches tall with their fans.



CNC machine tool with a bin of metal chips in a machine shop

Microchannel condenser, scroll compressors, touch-screen PLC and a stainless pump on one set of casters.

Request a Quote

NQ Series Air-Cooled Applications

Injection molding
Injection molding
Blow molding and packaging
Blow molding and packaging
Die casting
Die casting
Machine tools
Machine tools

schematic of the NQ series Air-Cooled circuit, showing where the process fluid and the condenser heat go

Portable, Air-Cooled, and In the Room

An air-cooled NQ puts its condenser heat into the space it sits in, roughly the cooling load plus the compressor work. A 30-ton unit beside a molding line adds something like 450,000 Btu/h to the building, which is why the larger air-cooled portables often end up against an outside wall, ducted, or replaced by a water-cooled or remote-condenser NQ. Thermal Care offers outdoor-duty construction as an option.

Size the chiller to the process at the set point it runs, not to the press tonnage. Mold cooling at 50°F matches the rating; a colder set point on glycol makes less than the listed tons. The leaving fluid temperature guide explains how much capacity each degree costs.

Every part-number page below names the Temptek air-cooled portable we supply in its place, sized to cover the NQ's published 50°F capacity. The NQA30, at 31 tons, is just above the largest Temptek portable, so its page names a Temptek air-cooled central chiller instead.
Call and talk it through with an engineer: 1-805-484-2992

NQ Air-Cooled Portables in Practice

Because the NQA20 is published at 21 tons at the 50°F rating point, and the selection covers that figure, not the 20 in the name. The CG-25A clears it by 3.5 tons. Thermal Care's ratings sit slightly above the model numbers on most sizes, 26 tons on the NQA25 and 31 on the NQA30, so sizing by name would leave each replacement short.

Often, if the discharge can be ducted with little added resistance, but the air path has to be designed, not improvised. Ducting takes the heat out of the room; the outdoor-duty option Thermal Care offers is for putting the unit itself outside. The heat to move is the load plus compressor work, so an NQA20 at its published 21 tons rejects more than 252,000 BTU/hr. The common mistake is a long or undersized duct the condenser fans cannot push through, which shows up as high head pressure on warm days. On the cabinets that stand 94 inches tall with fans on top, plan the duct transition against the ceiling height.

The NQV is the NQ built with a variable-speed scroll compressor, offered from 5 to 30 tons, so it follows the load continuously instead of cycling or unloading in steps. Thermal Care publishes no separate NQV model numbers, so those units are cross-referenced by the NQ size they are built on. If the nameplate says NQV, look up the matching NQA size and tell us it is the variable-speed version. A plant that bought one usually has a load that swings, a press that idles between shots or a line that changes molds through the shift, and the replacement's control should handle the same pattern.

No: the heat a chiller puts into a room follows the load it carries plus its compressor work, not its nameplate. If the process is the same 31 tons the NQA30 is published at, that is 372,000 BTU/hr of process heat with the compressor's share on top, whether the machine is rated 31 or 40 tons. What changes with the TTI-40A is the format: it is an air-cooled central chiller, not a portable, so floor space, piping and where its heat is discharged are planned with it. The 9 tons of headroom is margin for a hot afternoon, not added heat.