Thermal Care's workhorse portable: 4 to 31 tons, air-cooled with microchannel condensers, scroll compressors and a PLC with a 7-inch touch screen.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Portable Chiller | Air-Cooled Portable | 4 to 31 Tons | 9 |
Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.
Nine models, one or two scroll compressors. The NQA04 to NQA15 run one compressor and the NQA20 to NQA30 two, each into a stainless steel brazed plate evaporator with an electronic expansion valve, on R-454B or R-410A. Condensers are all-aluminum microchannel coils with TEAO fan motors and a cleanable inlet filter.
Capacity is published at 50°F leaving coolant and 95°F ambient. The unit pages list 4 to 31 tons, usually a little above the model number: the NQA10 at 11 tons, the NQA25 at 26. The set point range is 20 to 80°F.
Tank and pump grow in steps. Reservoirs run 14 to 67 gallons and the stainless process pump 2 to 5 hp, delivering 10 GPM at 43 PSI on the NQA04 up to 72 GPM at 43 PSI on the NQA30. Process connections are 1-1/2 inch to the NQA13 and 2 inch above.
It is loud at the top. Thermal Care publishes sound pressure at 1 meter of 74 dBA on the smallest units rising to 86 dBA on the NQA30, and the 15-ton and larger cabinets stand 94 inches tall with their fans.
Microchannel condenser, scroll compressors, touch-screen PLC and a stainless pump on one set of casters.
Request a Quote
An air-cooled NQ puts its condenser heat into the space it sits in, roughly the cooling load plus the compressor work. A 30-ton unit beside a molding line adds something like 450,000 Btu/h to the building, which is why the larger air-cooled portables often end up against an outside wall, ducted, or replaced by a water-cooled or remote-condenser NQ. Thermal Care offers outdoor-duty construction as an option.
Size the chiller to the process at the set point it runs, not to the press tonnage. Mold cooling at 50°F matches the rating; a colder set point on glycol makes less than the listed tons. The leaving fluid temperature guide explains how much capacity each degree costs.
Every part-number page below names the Temptek air-cooled portable we supply in its place, sized to cover the NQ's published 50°F capacity. The NQA30, at 31 tons, is just above the largest Temptek portable, so its page names a Temptek air-cooled central chiller instead.