Product Type Capacity Refrigerant
Portable Chiller Water-Cooled Portable 17 Tons @ 50°F R-454B or R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n NQW15 as shown on this page.

Replacement chiller for the Thermal Care NQW15

Description

The Thermal Care NQW15 is a water-cooled portable chiller from the Accuchiller NQ Series. Thermal Care publishes it at 17 tons (60 kW) at 50°F leaving coolant, 85°F condenser water, with a 20 to 80°F set point range. It runs one scroll compressor, on R-454B or R-410A. It carries a 30-gallon reservoir and a 3 hp process pump rated 39 GPM at 35 PSI. Replacement: we supply the Temptek CG-20W, a water-cooled portable chiller rated 20 tons at 50°F, against the 17 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
NQW15
Manufacturer:
Thermal Care
Replacement Unit:
Temptek CG-20W

Published Capacity

Cooling Capacity:
17 tons (60 kW)
Rating Basis:
50°F leaving coolant, 85°F condenser water
Set Point Range:
20 to 80°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
1
Refrigeration Circuits:
One
Refrigerant:
R-454B or R-410A
Condenser:
Water-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, 7-inch Color Touch Screen
Sound Pressure:
73 dBA at 1 m

Pump & Reservoir

  • Reservoir: 30 gallons
  • Process Pump: 3 hp
  • Pump Flow: 39 GPM
  • Pump Pressure: 35 PSI

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 41 A
  • Maximum Overcurrent Protection: 70 A

Connections

Process Connections:
1-1/2 in

Dimensions & Weight

Dimensions (L x W x H):
75 x 34 x 53 in
Shipping Weight:
1,315 lbs (596 kg)
Operating Weight:
1,500 lbs (680 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.