1-805-484-2992

Quotes - Sizing - Sales

TCR700Q

Thermal Care
Product Type Capacity Refrigerant
Central Chiller Remote Condenser 200 Tons @ 50°F R-513A or R-134a

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n TCR700Q as shown on this page.

Replacement chiller for the Thermal Care TCR700Q

Description

The Thermal Care TCR700Q is a centrifugal central chiller with remote air-cooled condensers from the Accuchiller TC Series. Thermal Care publishes it at 200 tons (703 kW) at 50°F set point, 60°F return, 95°F condenser air, one configuration of a frame its series table lists at 40 to 240 tons, with a 45 to 75°F set point range. It runs two Turbocor centrifugal compressors, on two refrigeration circuits, on R-513A or R-134a. Thermal Care pairs it with two LAVF-25312 remote air-cooled condensers. Replacement: no single Temptek unit reaches 200 tons, so we supply it from our sister line: add-on chiller modules for plant-wide systems to 300 tons, paired to the load.

Product Overview

Part Number:
TCR700Q
Manufacturer:
Thermal Care

Published Capacity

Cooling Capacity:
200 tons (703 kW)
Frame Capacity Range:
40 to 240 tons
Rating Basis:
50°F set point, 60°F return, 95°F condenser air
Set Point Range:
45 to 75°F

Configuration & Specifications

Compressor:
Turbocor Centrifugal, Magnetic Bearing
Compressors:
2
Refrigeration Circuits:
Two
Refrigerant:
R-513A or R-134a
Condenser:
Remote Air-Cooled
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC

Electrical

Voltage:
460V
Phase:
Three Phase
Frequency:
60 Hz
Minimum Circuit Ampacity:
409 A
Maximum Overcurrent Protection:
500 A

Connections

Process Connections:
6 in flange
Refrigerant Discharge Line:
3-1/8 in
Refrigerant Liquid Line:
2-1/8 in
Remote Condenser:
2 x LAVF-25312
Condenser Fans:
10 per condenser

Dimensions & Weight

Dimensions (L x W x H):
139 x 73 x 63 in
Shipping Weight:
4,134 lbs (1,875 kg)
Operating Weight:
4,526 lbs (2,053 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales