1-805-484-2992

Quotes - Sizing - Sales

TSEW020S

Thermal Care
Product Type Capacity Refrigerant
Central Chiller Water-Cooled Central 22 Tons @ 50°F R-454B or R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n TSEW020S as shown on this page.

Replacement chiller for the Thermal Care TSEW020S

Description

The Thermal Care TSEW020S is a water-cooled scroll central chiller from the Accuchiller TSE Series. Thermal Care publishes it at 22 tons (77 kW) at 50°F set point, 60°F return, 85°F condenser water, with a 20 to 80°F set point range. It runs two scroll compressors, on R-454B or R-410A. An integral tank is an option: 275 gallons with process and chiller pumps as standard, or 400 gallons on the high-flow package. Replacement: we supply the Temptek MW-25-C, a water-cooled chilling module rated 25 tons at 50°F, against the 22 tons Thermal Care publishes for this unit at 50°F. Both makers rate at 50°F leaving fluid, so the comparison is like for like. It is refrigeration only, like this chiller without its tank option, and works with a pump-tank station.

Product Overview

Part Number:
TSEW020S
Manufacturer:
Thermal Care
Replacement Unit:
Temptek MW-25-C

Published Capacity

Cooling Capacity:
22 tons (77 kW)
Rating Basis:
50°F set point, 60°F return, 85°F condenser water
Set Point Range:
20 to 80°F

Configuration & Specifications

Compressor:
Scroll
Compressors:
2
Refrigeration Circuits:
One
Refrigerant:
R-454B or R-410A
Condenser:
Water-Cooled, Cleanable
Evaporator:
Stainless Steel Brazed Plate
Controls:
PLC, Color Touch Screen

Pump & Reservoir

  • Tank Option, Standard Flow: 275 gallons, 5/1.5 hp process / chiller pumps
  • Tank Option, High Flow: 400 gallons, 10/1.5 hp process / chiller pumps

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • Minimum Circuit Ampacity: 48 A
  • Maximum Overcurrent Protection: 70 A

Connections

Process Connections:
2 in
Condenser Water Connections:
2 in

Dimensions & Weight

Dimensions (L x W x H):
75 x 30 x 68 in
Shipping Weight:
1,149 lbs (521 kg)
Operating Weight:
1,179 lbs (535 kg)

Specifications sourced from Thermal Care's published unit pages and series specification tables (thermalcare.com), September 2026. Thermal Care, Accuchiller and the series names shown are trademarks of their owner; referenced here for cross-reference only. Turbocor is a trademark of its owner. Confirm against the unit nameplate before ordering.